Vertical through the roof applications, Elbows. b) up to two 45, Elbows 7 ft – Vermont Casting BHDR36 User Manual

Page 24

background image

- 24 -

DO NOT BACK FILL AROUND SNORKEL.
SOIL SHOULD NOT BE LESS THAN 4"
BELOW SNORKEL.

FOUNDATION

RECESS

SNORKEL

SCREWS

WALL

SCREWS

SHEET METAL

WATERTIGHT

SEAL

AROUND

PIPE

If the foundation is recessed, use recess brackets (not
supplied) for securing lower portion of the snorkel. Fasten
brackets to wall first and then secure to snorkel with self
drilling #8 x 1/2 sheet metal screws. It will be necessary to
extend vent pipes out as far protruding wall face (Fig. 57).

Fig. 57

MAXIMUM

10 FT

(3048mm)

PIPE STRAPS

EVERY 3'

(914mm)

MINIMUM

8 FT./

MAXIMUM

40 FT.

VERTICAL

RISE

VERTICAL THROUGH THE

ROOF APPLICATIONS

This Gas Fireplace has been approved for,
a) Vertical installations up to 40 feet (12 metres) in height.

Up to a 10 ft. horizontal vent run can be installed within
the vent system using a maximum of three 90

o

elbows.

b) Up to two 45

o

elbows may be used within the horizontal

run. For each 45

o

elbow used on the horizontal level

the maximum horizontal length must be reduced by 18
inches.

Example: Maximum horizontal length

0

-

45

o

elbows

10 ft.

1

-

45

o

elbows

8.5 ft.

2

-

45

o

elbows

7 ft.

Fig. 58

Fig. 62

The minimum height of the vent above the highest
point of penetration throught the roof is 2 feet. See
Fig. 62.

ATTIC INSULATION

SHIELD

JOISTS

ROOF

VENT TERMINATION

ATTIC INSULATION

ROOF SUPPORT

STORM COLLAR

ROOF FLASHING

24" Min.
(610mm)

CEILING JOISTS

40 FEET
(12.2m)

TYPICAL STRAIGHT-UP INSTALLATION

)

TYPICAL 7DVCS

APPLICATION

TYPICAL ROOF

SUPPORT

APPLICATION

Fig. 59

Fig. 60

Fig. 61

c)

A minimum of an 8 ft. vertical rise.

d) Two sets of 45 degree elbow offsets within these

vertical installations. From 0 to a maximum of 8 ft. a
vent pipe can be used between elbows. (Fig. 59)

e) 7DVCS must be used to support offsets. (Fig. 60)
This application will require that you first determine the roof
pitch and use the appropriate 7TDVSKV (A,B or F). (see
Venting Components, page 27)

SIDE VIEW

MAX.

40 FEET

(12.2m)

MIN.

8 FEET

(2.44m)

MAX. 8 Ft.
(2438mm)

MAX. 8 Ft.
(2438mm)