beautypg.com

Vertical thru the roof installation – Vermont Casting BHDR36 User Manual

Page 16

background image

- 16 -

Fig. 36

The minimum height of the vent above the highest
point of penetration throught the roof is 2 feet. See
Fig. 36.

TYPICAL STRAIGHT-UP INSTALLATION

40 FEET

(12.2m)

ATTIC INSULATION

SHIELD

JOISTS

ROOF

VENT TERMINATION

ATTIC INSULATION

ROOF SUPPORT

STORM COLLAR

ROOF FLASHING

2' Min.

CEILING JOISTS

1.

Locate your fireplace.

2.

Plumb to centre of the (4") 90

o

transition elbow

(7DVRT90) from ceiling above and mark position.

3.

Cut opening equal to 9-3/8" x 9-3/8" (240 mm x 240
mm).

4.

Proceed to plumb for additional openings through the
roof. In all cases, the opening must provide a minimum
of 1 inch clearance to the vent pipe, i.e., the hole must
be at least 9-3/8" x 9-3/8" (240 mm x 240 mm).

5.

Place fireplace into position and secure to floor.

6.

Place firestop(s) #7DVFS into position and secure.
(Fig. 37)

7.

Install roof support (Fig. 35) and roof flashing making
sure upper flange of flashing is below the shingles.
(Fig. 38)

8.

Install appropriate pipe sections until above the flash-
ing. (See Fig. 36 for #'s 7, 8 and 9).

9.

Install storm collar and seal around the pipe.

10. Add additional vent lengths for proper height. (Fig. 36)
11. Apply high temperature sealant to 4" and 7" collars of

vent termination and install.

VERTICAL THRU THE

ROOF INSTALLATION

Fig. 37 If there is a room above ceiling level,
firestop spacer must be installed on both the
bottom and the top side of the ceiling joists. If an
attic is above ceiling level a 7DVAIS (Attic
Insulation Shield) must be installed.

Fig. 38 The enlarged ends of the vent section
always face downward.

SEALANT

SHEETMETAL
SCREWS (#5) —
3 PER JOINT

STORM
COLLAR

JOIST

11"

11"

Attic
Insulation
Shield

Ceiling
Installation

JOIST

NAILS (4)

FIRESTOP
SPACER

11"

11"

UPPER FLOOR

45

°

45

°

2438m

MAX.

8 FEET

2438m

MAX.

8 FEET

40'(12.2m)

TYPICAL OFFSET INSTALLATION

TYPICAL 7DVCS

APPLICATION

TYPICAL ROOF

SUPPORT

APPLICATION

Fig. 33

Fig. 34

Fig. 35

Fig. 38

Fig. 37

c)

A minimum of an 8 ft. vertical rise.

d) Two sets of 45 degree elbow offsets within these

vertical installations. From 0 to a maximum of 8 ft. a
vent pipe can be used between elbows. (Fig. 33)

e) 7DVCS must be used to support offsets. (Fig. 34)
This application will require that you first determine the roof
pitch and use the appropriate 7DVSKV (A,B or F). (see
Venting Components, page 18)