PC15CP PUMP CONTROLLER OPERATION / MAINTENANCE MANUAL
PAGE 9
3
REMOTE OPERATION
To operate the controller by a remote signal, the following conditions must be met:
Input 1 (I1) must have a source input sufficient (>9 VDC) to activate the input as
indicated in the display below to activate the remote operation capabilities.
Input 2 (I2) must have a switched source input sufficient (>9 VDC) to activate the
input in conjunction with I1 to turn the controller ON (High Signal) or OFF (Low
Signal) as shown in the display below.
Figure 8: Remote Mode (ON)
Figure 9: Remote Mode (OFF)
During remote operation, the controller can be manually stopped by pressing the RIGHT
arrow key () from the HOME page, this will locally stop controller oscillation. While in the
override stop state, the cursor under the position 8 will be ON (Figure 8).
To resume pump operation toggle input I2 changing its state (ON state to the OFF state)
resetting output 8 and then turning I2 on again. In order to turn the controller on locally exit
out of remote mode (I1 = OFF) then from the Home Page, press the RIGHT arrow key ()
will start and stop the control of the pump as normal.
Figure 10: Local Override Stop Display
Pump status feedback is provided on output Q3. As indicated in Figure 8 and 9 this output
may be wired to provide an indication signal of pump operation