1 nominal size, 2 nozzle loads, 3 suction line – Richter MNK-B Series User Manual
Page 11: 4 supply lines, 5 discharge line, 6 venting and evacuating, 5 pipe fittings, Nominal size, Nozzle loads, Suction line

Series MNK-B,
close-coupled design
Page 11
9230-055-en
Revision 09
TM 7345
Edition 10/2008
5.4.1 Nominal size
The operating design point of a centrifugal pump lies 
at the intersection of the pump curve and the pipe 
curve, see Fig. 2. The pump curve is provided by the 
pump manufacturer. The pipe curve is determined 
using diagrams or PC programs. 
Fig.2
Under no circumstances can the nominal size of the 
piping be derived from the connected nominal size of 
the pump. 
The pipe nominal size can also be determined using 
the flow rate as a rough guide. 
)
m
(
A
)
s
/
m
(
Q
)
s
/
m
(
v
2
3
=
The velocity in the suction line should not exceed 
2.0 m/s and 5.0 m/s in the discharge line. 
When determining the suction line nominal size, the 
NPSH value (net positive suction head) must also be 
observed. The 
NPSHR value
required for the pump is
specified in the data sheet.
The NPSHR available in the plant 
should be at least 0.5 m higher than 
the NPSHR required for the pump. 
Otherwise, this will lead to a drop in the delivery head, 
cavitation or even failure of the pump. 
 
5.4.2 Nozzle loads
The pump can be subjected to nozzle loads in 
accordance with ISO 5199. 
See also 
TIS 0541-02-0006
.
Changes in the length of the piping caused by 
temperature are to be allowed for by appropriate 
measures, e.g. the installation of expansion joints. 
 
5.4.3 Suction line
The suction lines must always be laid on a rising 
gradient towards the pump. Otherwise, gas bubbles 
may form which considerably reduce the suction line 
cross section. Eccentric transition elements must be 
installed between different pipe diameters. 
Valves which disrupt the course of flow should not be 
installed directly upstream of the pump. 
Fig. 3
5.4.4 Supply lines
Supply lines should vent towards the reservoir and are 
therefore to be laid with a constant downward gradient 
towards the pump. Should the piping internals 
upstream of the pump be horizontal, a low point can, 
of course, be located upstream of these internals. 
From here the pipe is then laid with an upward 
gradient to the pump so that the gas bubbles which 
form here can escape through the pump. 
Valves which disrupt the course of flow should not be 
installed directly upstream of the pump. 
 
5.4.5 Discharge line
Do not arrange the shut-off valve directly above the 
pump but initially provide a transition section. 
The discharge nozzle velocity of the medium can – if 
necessary – be reduced. 
 
5.4.6 Venting and evacuating
Venting can take place into the discharge line or 
upstream of the discharge valve. 
A venting line can also be used as a bypass, drain or 
flushing line. 
The pump housing is fitted with a drain connection as 
a standard feature. Optionally, the drain bore can be 
drilled. Boring template see 
Section 10.1
.
Fig. 4
5.5 Pipe fittings
The following pipe fittings are available from Richter 
on request: 
Shut-off valves 
Check valves 
Sight glasses 
Priming vessels 
Strainers 
Pressure gauges 
