Headloss
Flow Rate - Gallons per minute (Water)
Pressure Drop (psi)
Angle
Globe
100
80
60
40
30
20
10
8
6
4
3
2
Maximum continuous flow based on velocity of 20 ft. per second.
Maximum intermittent flow based on velocity of 25 ft. per second.
The C
v
Factor of a value is the flow rate in US GPM at 60°F that will cause a 1psi drop in pressure.
The factors stated are based upon a fully open valve.
C
v
factor can be used in the following equations to determine Flow (Q) and Pressure Drop (∆P):
Q (Flow) = C
v
√∆P ∆P (Pressure Drop) = (Q/C
v
)
2
ES-ACV-S400-S1400 1219
© 2012 Watts
USA: Tel. (713) 943-0688 • (713) 944-9445 • www.watts.com
A Watts Water Technologies Company
2
4
6 8 10
20
40
60 80 100
200
500
1000
2000
5000
10000
20000
S400 / S1400 — Full Port Stainless Steel Single Chamber Basic Valve
with Mechanical Check Feature
Flow Data - ACV S400 (Globe) / S1400 (Angle)
Valve Size - Inches
4
6
8
10
12
16
Maximum Continuous
Flow Rate Gpm (Water)
800
1850
3100
5000
7000
11100
Maximum Intermittent
Flow Rate Gpm (Water)
1000
2300
4000
6250
8900
14100
C
V
Factor GPM (Globe)
210
460
790
1260
1725
2940
C
V
Factor GPM (Angle)
250
561
990
1590
2500
4200
Estimated
Valve Cover Chamber Capacity
Valve Size - Inches
4
6
8
10
12
16
fluid oz.
22
70
U.S. Gal
1-1/4
2-1/2
4
9-1/2
Valve Travel
Valve Size - Inches
4
6
8
10
12
16
Travel - Inches
1
1-1/2
2
2-1/2
3
4
4
6
8
10
12
16
4
6
8
10
12
16