Classic Series
PRESSURE REDUCING and
SUSTAINING VALVE with
SURGE CONTROL FEATURE
F115-43 (Globe)
F1115-43 (Angle)
Installation Guidelines
• Prior to installation, flush line to remove debris.
• Install valve horizontally “in line” (cover facing up), so flow arrow matches flow through the line. Avoid
installing valves 6” and larger vertically. Consult factory prior to ordering if installation is other than
described.
• Install inlet and outlet isolation valves. NOTE: When using butterfly valves, insure disc does not contact
control valve. Damage or improper valve seating may occur.
• Provide adequate clearance for valve servicing and maintenance.
• Install pressure gauges to monitor valve inlet and outlet pressure.
• If installation is subjected to very low flow or potentially static conditions, AMES recommends a pressure
relief valve (1/2” minimum) be installed downstream of the Pressure Reducing Valve for additional system
protection.
Other Watts ACV Pressure Reducing Control Valves
F115 / F1115
Pressure Reducing Valve
F115-2 / F1115-2
Pressure Reducing and Sustaining Valve
F115-3 / F1115-3
Pressure Reducing Valve with Hydraulic Check Feature
F115-4 / F1115-4
Pressure Reducing Valve with Solenoid (On-Off) Feature
F115-7 / F1115-7
Pressure Reducing Valve with Downstream Surge Control Feature
F115-11 / F1115-11 Pressure Reducing and Sustaining Valve with Hydraulic Check Feature
F115-58 / F1115-58 Pressure Reducing Valve with Return Flow Feature
F115-74 / F1115-74 Pressure Reducing Valve with Low Flow By-Pass