Headloss, Valve cover chamber capacity, Valve travel – Watts M6400 / M61400 User Manual

Page 2

background image

Headloss

Flow Rate - Gallons per minute (Water)

Pressure Drop (psi)

Angle
Globe

2

4

6 8 10

20

40

60 80 100

200

500

1000

2000

5000

10000

20000

100

80

60

40

30

20

10

8

6

4

3

2

Maximum continuous flow based on velocity of 20 ft. per second.
Maximum intermittent flow based on velocity of 25 ft. per second.
The C

v

Factor of a value is the flow rate in US GPM at 60°F that will cause a 1psi drop in pressure.

The factors stated are based upon a fully open valve.
C

v

factor can be used in the following equations to determine Flow (Q) and Pressure Drop (∆P):

Q (Flow) = C

v

√∆P ∆P (Pressure Drop) = (Q/C

v

)

2

ES-ACV-M6400-M61400 1219

© 2012 Watts

USA: Tel. (713) 943-0688 • (713) 944-9445 • www.watts.com

A Watts Water Technologies Company

M6400-M61400— Reduced Port Ductile Iron Single Chamber Basic Valve
with Mechanical Check Feature

Flow Data - ACV M6400 (Globe) / M61400 (Angle)

Valve Size - Inches

4

6

8

10

12

16

18

20

24

Maximum Continuous

Flow Rate Gpm (Water)

485

800

1850

3100

5000

7000

11100

11100

11100

Maximum Intermittent

Flow Rate Gpm (Water)

590

1000

2300

4000

6250

8900

14100

14100

14100

CV Factor GPM (Globe)

133

224

489

932

1428

2067

2881

2881

2881

CV Factor GPM (Angle)

132

237

534

Estimated

Valve Cover Chamber Capacity

Valve Size - Inches

4

6

8

10

12

16

18

20

24

fluid oz.

10

22

70

U.S. Gal

1-1/4

2-1/2

4

9-1/2

9-1/2

9-1/2

Valve Travel

Valve Size - Inches

4

6

8

10

12

16

18

20

24

Travel - Inches

3/4

1

1-1/2

2

2-1/2

3

4

4

4

4

6

8

10

12

16

18/20/24

4

6

8