beautypg.com

Dimensions - weights, Feed water guidelines, Specifications – Watts PWR4022 User Manual

Page 2: Performance, Ordering information

background image

Dimensions - Weights

Model No.

diMeNsioNs

WeiGHTs

A B C

in. mm in. mm in. mm lbs. kg

PWR40223083

24

610 68

1727 94 2388 800 364

PWR40223103

24

610 68

1727 94 2388 900 409

PWR40223123

24

610 68

1727 94 2388 1000 455

Feed Water Guidelines

pH . . . . . . . . . . . . . . . . . . . . . . . . 6 to 9
Hardness (maximum) . . . . . . . . . . Less than 1 grain per gal-

lon as CaCO3 (Softened)

or anti scale chemical

injection if not softened

(contact your Watts

representative)

Feed Water Pressure (minimum) . . 20psi
Temperature . . . . . . . . . . . . . . . . . 35 - 100°F (2 - 38°C)
Free Chlorine (maximum). . . . . . . . None Allowed
Iron (maximum) . . . . . . . . . . . . . . . Less than .1mg/L
Oil and H2S . . . . . . . . . . . . . . . . . None Allowed
Turbidity . . . . . . . . . . . . . . . . . . . . Less than 1.0 NTU
Silt Density Index . . . . . . . . . . . . . Less than 5.0 SDI

Notes:
* For all other guideline information please contact your Watts representative.
* Published maximum production rates are based on a feed water of 77°F,

SDI of less than 3, 1000 ppm TDS, and pH 8. Individual membrane pro-

ductivity may vary (± 15%). May be operated on other feed waters with

reduced capacity.

* Percent rejection is based on membrane manufacturer’s specifications;

overall system percent rejection may be less.

Specifications

Watts Pure Water Series PWR4022 reverse osmosis system

shall be installed to provide reverse osmosis quality water. The

RO system shall be installed after a Series PWS water softener

so that scale forming calcium and magnesium hardness cannot

scale the RO membranes. Series PWC backwashing carbon fil-

ter shall be installed on the RO feed water line to remove chlo-

rine and prevent membrane degradation due to chlorine attack.

Series PWM backwashing sediment filter shall also be installed

on the RO feed water line to reduce the silt density index of the

water to prevent particulate fouling of the RO membranes.
The RO system shall be a high-pressure/high-rejection type

unit complete with permeate and reject water flow meters,

reject recycle water flow meter, pre-filter inlet and outlet pres-

sure gauges, membrane feed and reject water pressure gaug-

es, FRP membrane housings, automatic inlet solenoid valve,

low feed water pressure switch, reject and recycle valves,

digital controller with conductivity meter and high-conductivity

alarm output, storage tank level and pretreatment interlock

inputs, 7.5 horse power multistage centrifugal high pressure

pump, and all other components necessary for proper opera-

tion. The system shall be a floor mount design. The RO perme-

ate water shall be collected in an atmospheric storage tank

with the tank level controlled by an electronic level float. The

RO shall be equipped with inputs for the tank level float as well

as pretreatment interlock to shut the RO system down in the

event the pretreatment begins a backwash cycle. Electrical

requirements are 230 volt 60 hertz three phase. A local drain is

required to accept drain water from the system. The feed water

pressure must not fall below 20psi. The feed water tempera-

ture must not fall below 35°F or exceed 100°F (2 - 38°C).
The system shall produce reverse osmosis quality water with

97 percent minimum average ionic rejection of total dissolved

solids when operated within the manufacturer’s operational

specifications.

FRONT

SIDE

C

FRoNT

FRONT

SIDE

B

A

side

ES-WQ-PWR4022 1122

© 2011 Watts

USA: North Andover, MA • Tel. (800) 224-1299 • www.watts.com

Canada: Burlington, ON • Tel. (888) 208-8927 • www.wattscanada.ca

A Watts Water Technologies Company

Maximum Productivity (gallons per minute)

10

12.5

15

Quality (typical membrane percent rejection)

98 %

Recovery (adjustable)

60 - 75 %

Membrane Size

4" x 40"

Membrane Array (two elements per vessel)

2:1:1

2:2:1

3:2:1

Prefilter (system ships with one 5 micron cartridge)

20" Big Blue

Feed Water Connection

1" FNPT

Product Water Connection

1" FNPT

Reject Water Connection

3

4

" FNPT

Feed Water Required (GPM at 65% recovery)

17

21

25

Minimum Feed Water Pressure

20 psig

Drain Required (maximum)

17

21

25

Electrical Requirement (other voltages available) 230 VAC, 3-phase, 60 Hz, 20 amps
Motor Horse Power / Type

7.5 / TEFC

Dimensions L x W x H (approximate)

96" x 24" x 72"

Shipping Weight (estimated pounds)

800

900

1000

Performance

Model No.

description

PWR40223083

10 GPM Reverse Osmosis System with Micro Processor Control
and Auto Flush

PWR40223103

12.5 GPM Reverse Osmosis System with Micro Processor
Control and Auto Flush

PWR40223123

15 GPM Reverse Osmosis System with Micro Processor Control
and Auto Flush

Ordering Information