beautypg.com

Installation instructions, Series 007dcda, Indoor installations – Watts 007DCDA User Manual

Page 2: Outdoor installations, Below ground installations, Parallel installations

background image

Installation Instructions

Series 007DCDA

2

Annual inspection of all water system safety and valves is
required. Regular inspection, testing and cleaning assures
maximum life and proper product function.
The Series 007DCDA may be installed in either a horizontal or

vertical-up orientation for service on commercial potable water

or fire sprinkler systems. Supply pipe lines should be thoroughly

flushed to remove foreign material before installing the unit that

may cause unnecessary check fouling. The backflow assembly

must be installed with the arrow on the valve body pointing in the

direction of flow for proper operation.
It is recommended this device is installed downstream of a water

meter and/or main line insolation shutoff valves with installation

techniques that comply with the latest edition of the Uniform

Plumbing Code. Please consult Local Governing Code for proper

installation and agency code requirements.

CAUTION

!

Strainer Installations
The installation of a strainer upstream of the Backflow Assembles

is recommend to prevent the check modules from unneces-

sary fouling when used on commercial potable water systems.

DO NOT install a strainer when the Backflow Preventer is called

upon for emergency deluge or used on a fire sprinkler system

and/or individual sprinkler feed.

CAUTION

!

Fire Protection System Installations
The National Fire Protection Agency (NFPA) Guidelines require

a confirming flow test to be conducted whenever a “main line”

valve such as the shutoff valves or a backflow assembly have

been operated. A Certified Backflow Tester must conduct this

test. The trim valves located on the detector meter bypass line (if

equipped) should be fully closed during the confirming flow test

of the “main line” Backflow Assembly. Once complete, the trim

valves must be returned to a fully open position.

CAUTION

!

Flange Connections
It is recommended to inspect and retighten all flange gasket

bolts on the Backflow Assembly during installation. Flange

gasket bolts may have loosened due to storage, transport and/or

static system hydro-testing.

Indoor Installations

For indoor installation, it is important the Backflow Assembly be

easily accessible to facilitate testing, “main line” valve servic-

ing and/or removal of the detector meter bypass line.

DO NOT

install a Backflow Assembly in a concealed location.

Outdoor Installations

For outdoor installations, care must be taken to ensure the Back-

flow Assembly is not subjected to periods of freezing conditions.

Freezing conditions may damage the product and produce a

non-operational assembly. If the installation is subjected to freez-

ing conditions, the use of an insulated and/or heated enclosure

(WattsBox) may be required.

Below Ground Installations

The Series 007DCDA is not recommend for below ground (burial)

installations. The most satisfactory installation is above ground

and should be installed in this manner whenever possible. If

below ground installation is required, the use of a “valve box” to

shield the Backflow Assembly from contact with soil organics

and provide adequate drainage in the event of rain-fall is recom-

mended. Consult your Local Governing Code for proper below

ground installation and agency code requirements.

Parallel Installations

Two or more Series 007DCDA Backflow Assemblies may be

piped in parallel (where approved by Local Governing Code)

to serve a larger supply pipe main. This type of installation is

employed whenever it is vital to maintain a continuous supply

of water, where interruptions for testing and servicing would be

unacceptable. Parallel installations also provide an advantage

to increase capacity where needed beyond that provided by a

single Backflow Assembly and permits testing or servicing of an

individual assembly without shutting down the complete line. For

two valve installations, the total capacity should equal or exceed

the total requirement of the system.