beautypg.com

No. tk-9 model “a” test kit, Test set up, Test procedure – Watts TK-9A User Manual

Page 2: Test no. 1, Test no. 2, Test no. 3, Test no. 4

background image

2

Reduced Pressure Zone Backflow Preventers must be

inspected and tested periodically,

in accordance with local codes, to ensure proper operation of

check valves within the unit. A differential pressure gauge is

recommended for Test No. 1 rather than a manometer for the

following reasons: It utilizes minimum time to perform the test.

It eliminates the necessity of closing the inlet ball valve which

could release pipe scale and foreign matter into the backflow

preventer. Only a slight amount of water is ‘spilled’ in test. A

mercury manometer could cause a pollution hazard.

Test Set Up

Reduced Pressure Zone Assembly
Close Valves A, B and C on Test Kit.
Connect high side hose to test cock #2
Connect low side hose to test cock #3. Close shutoff #2.
Open test cocks #2 and #3.
Open vent valve C.
Open ‘high’ valve A and bleed to atmosphere until all the air

is expelled.
Close valve A. Open ‘low’ valve B and bleed to atmosphere until

all air is expelled. Close ‘low’ valve B. Close ‘vent’ valve C.
Connect vent hose to test cock #4.

Test Procedure

Reduced Pressure Zone Assembly
Field Test Equipment Required
Reduced Pressure Zone Backflow Preventer Test Kit

Test No. 1

Purpose: To test check valve No. 2 for tightness against re-

verse flow.
Requirements: Valve must be tight against reverse flow under

all pressure differentials. Slowly open the high valve A and

the vent valve C, and keep the low valve B closed. Open test

cock #4. Indicated pressure differential will decrease slightly. If

pressure differential continues to decrease (until the vent opens)

check valve #2 is reported as leaking.

Test No. 2

Purpose: To test shutoff #2 for tightness.
Requirements: After passing Test No. 1, continue to Test No.

2 by closing test cock #2. The indicated pressure differential will

decrease slightly. If pressure differential continues to decrease

(approaching “zero”), shutoff #2 is reported to be “leaking”.

Test No. 3

Purpose: To test Check Valve No. 1 for tightness.
Requirements: Valve must be tight against reverse flow under

all pressure differentials. Close high valve A and open test cock

#2. Close test cock #4. Disconnect vent hose at test cock #4.

Open valves B and C, bleeding to atmosphere. Then closing

valve B restores the system to a normal static condition. Ob-

serve the pressure differential gauge. If there is a decrease in the

indicated value, Check Valve No. 1 is reported as “leaking”.

Test No. 4

Purpose: To test operation of pressure differential relief valve.
Requirements: The pressure differential relief valve must

operate to maintain the “zone” between the two check valves

at least 2 psi less than the supply pressure. Close vent valve

C. Open high valve A. Open the low valve B very slowly until

the differential gauge needle starts to drop. Hold the valve at

this position and observe the gauge reading at the moment the

first discharge is noted from the relief valve. Record this as the

opening differential pressure of the relief valve.

NOTICE

It is important that the differential gauge needle drops slowly.
Close test cocks #2 and #3. Use vent hose to relieve pressure

from test kit by opening valves A, B and C. Remove all test

equipment and open shutoff #2.

Ball Type

Test Valves

(A)

(C)

(B)

Needle

Valve

Auxiliary

Test Cock

High Hose

(Color - Yellow)

Low Hose

(Color - White or Red)

Vent Hose

(Color - Blue)

Test Cock

No. 1

Test Cock

No. 2

Test Cock

No. 3

Test Cock

No. 4

Shutoff

No. 1

Check Valve

No. 2

Shutoff

No. 2

Check Valve

No. 1

909QT shown

CAUTION

!

To prevent freezing, hold Test Kit vertically to drain
differential gauge and hoses prior to placing in case.

No. TK-9 Model “A” Test Kit