For Commercial Applications

ES-WQ-PWR8024

Job Name –––––––––––––––––––––––––––––––––––––––––––

Contractor ––––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Engineer –––––––––––––––––––––––––––––––––––––––––––––

Contractor’s P.O. No. ––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Representative ––––––––––––––––––––––––––––––––––––––––

Series PWR8024

Series PWR8024

Commercial Reverse Osmosis

Systems

Flow Rates: Up to 100 gpm (378 lpm)

Watts Pure Water Series PWR8024 reverse osmosis (RO) systems

are commercial grade high-pressure RO units for the reduction of

total dissolved solids from water. They are designed to supply reverse

osmosis quality water with production rates ranging from 40 to 100

gallons per minute (151 to 379 lpm). These units are designed for floor

mount installations. Reverse osmosis is a process where high-pressure

feed water is fed into a semi-permeable membrane. In the membrane,

pure water is allowed to pass through the membrane material and exit

as purified permeate water. Dissolved mineral salts are not allowed

to pass through the membrane and become a concentrated reject

stream that is sent to a drain. These RO systems use high-pressure/

high-rejection membranes to achieve a minimum average NaCl ionic

rejection of 99 percent.
Watts Pure Water Series PWR8024 RO systems are a well designed,

rugged line of purifiers. This series comes with a pre-selected assort-

ment of features, including our digital controller, for monitoring and

operation. Corrosion resistant fiberglass reinforced plastic (FRP) mem-

brane housings, inlet and outlet pre-filter pressure gauges, 316 stain-

less steel membrane feed water piping, low-pressure switch with pro-

grammable delayed auto restart, inputs for tank level and pretreatment

interlock, conductivity meter with percent ionic rejection displayed,

high-conductivity alarm output, adjustable reject recycle, permeate and

reject water flow meters, reject recycle flow meter, permeate water

check valve, inlet diaphragm valve, membrane feed and reject water

pressure gauges, programmable auto flush, and adjustable reject valve

are all standard features.
These systems are designed to feed an atmospheric storage tank for

collection of the reverse osmosis water. Reverse osmosis water has

a wide variety of applications including municipal water treatment,

steam boiler and steam sterilizer make up, laboratory use, spot free

rinsing, ice and beverage water, water for cooking, food processing,

metal plating and finishing, as well as water for humidification. Reverse

osmosis is also the pretreatment of choice for ion exchange type de-

ionization (DI) systems. Using RO water as make up to a DI system

reduces the exhaustion rate of the DI resin by up to 95 percent saving

time, money, and chemicals associated with DI resin regeneration.

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

Features

• Membrane Auto Flush
• Powder coated carbon steel support frame
• Corrosion resistant 300psi FRP high-pressure membrane

housings

• Pressure gauges for pre-filter inlet/outlet, pump discharge,

membrane feed, and reject water pressure

• Low feed water pressure safety switch
• Digital microprocessor based controller with delayed auto

restart after low pressure shut down

• Permeate Water Conductivity meter with high conductivity

alarm output and percent ionic rejection displayed

• Tank level and pretreatment interlock inputs
• High-pressure/high-rejection membranes with 99% minimum

average salt rejection

• Permeate, reject recycle, and reject water flow meters
• Adjustable reject and reject recycle valves
• Permeate check valve
• Automatic inlet diaphragm valve

Standards

Membranes- Certified to NSF/ANSI Std. 61

PURE WATER

Note:

Do not use with water that is microbiologically unsafe or of

unknown quality without adequate disinfection before or after the sys-

tem.