Watts 6115-JM User Manual
Jm series pressure
![background image](/manuals/590229/1/background.png)
8550 Hansen Road . Houston, TX 77075 . Telephone 713.943.0688 . FAX 713.944.9445 www.wattsacv.com
JM Series Pressure
JM Series Pressure
Reducing Control Valve
Reducing Control Valve
The Automatic Answer to Fluid Control
DESCRIPTION
DESCRIPTION
•
4" ANSI 150 FF flanged
•
250 psi MWP
•
Designed for retrofit applications with
compact 12-1/4" laying length
•
Pilot operated design offers
exceptional flow characteristics
without “reduced pressure fall-off”
•
Directly replaces low capacity line
size regulators
UNIQUE FEATURES
UNIQUE FEATURES
•
3/4" Low-Flow By-Pass connections
•
Top and bottom guided stem
provides accurate low-flow throttling
•
100% NSF Approved heat fusion
bonded epoxy greatly reduces
corrosion and extends valve life
•
Inlet and outlet pressure gauge
connections
•
Adjustable Opening Speed Control &
Valve Position Indicator standard
•
30 – 300 psi adjustment range
APPLICATIONS
APPLICATIONS
•
Industrial
•
Commercial
•
Municipal
S P E
S P E CIFICATIONS
CIFICATIONS
•
Body and Cover:
-
Globe Pattern Reduced Port
-
Ductile Iron
-
NSF Approved epoxy coating
•
Seat:
-
Stainless Steel, AISI 316
•
Stem:
-
Stainless Steel, AISI 303
•
Spring:
-
Stainless Steel, AISI 303
•
Elastomers:
-
Diaphragm – FDA approved
Buna-N
-
Seat Disc – Buna-N