Direct side tapping, For heaters with direct top tapping, Dimensions — weights – Watts LFLLL100XL User Manual
Page 2
![background image](/manuals/590208/2/background.png)
Direct Side Tapping
Vertical discharge line must be installed with its direction downward.
For Heaters with Direct Top Tapping
Use standard or extra length extension thermostat.
Max. 6"
(152mm)
Insulation
Discharge
Line
Dimensions — Weights
NO.
SIZE
HEIGHT
C.S.A. TEMP
MODEL
LESS THERMOSTAT
WIDTH
WEIGHT
STEAM RATING
inches
mm
inches
mm
inches
mm
lbs.
Kgs.
BTU/Hr
LFSL100XL
3
⁄
4
20
4
102
1
7
⁄
8
48
.58
.26
105,000
Z5
LFL100XL
3
⁄
4
20
4
1
⁄
4
108
1
7
⁄
8
48
.61
.28
105,000
Z5
LFLL100XL
3
⁄
4
20
4
3
⁄
4
127
1
7
⁄
8
48
.65
.29
105,000
M7
LFLLL100XL
3
⁄
4
20
5
1
⁄
4
133
1
7
⁄
8
48
.68
.31
105,000
Z5
WARNING: REINSPECTION OF T&P RELIEF VALVE: Temperature and Pressure Relief Valves should be reinspected AT LEAST ONCE EVERY THREE
YEARS by a licensed plumbing contractor or authorized inspection agency, to insure that the product has not been affected by corrosive water conditions
and to insure that the valve and discharge line have not been altered or tampered with illegally. Certain naturally occurring conditions may corrode the
valve or its components over time, rendering the valve inoperative. Such conditions are not detectable unless the valve and its components are physically
removed and inspected. Do not attempt to conduct this inspection on your own. Contact your plumbing contractor for a reinspection to assure continuing
safety. FAILURE TO REINSPECT THIS VALVE AS DIRECTED COULD RESULT IN UNSAFE TEMPERATURE OR PRESSURE BUILD-UP WHICH CAN RESULT
IN SERIOUS INJURY OR DEATH AND/OR SEVERE PROPERTY DAMAGE.
IMPORTANT: A relief valve functions in an emergency by discharging water. Therefore, it is essential that a discharge line be piped from the valve in order
to carry the overflow to a safe place of disposal. The discharge line must be the same size as the valve outlet and must pitch downward from the valve and
terminate at least 6"(152mm) above the floor drain where any discharge will be clearly visible. For 100DT discharge line consult your Watts agent.
Series LFSL100XL, LFL100XL, LFLL100XL and LFLLL100XL
Model LFSL100XL Suitable for water heaters with up to
1
3
⁄
4
" (44mm) of insulation
Model LFL100XL
Suitable for water heaters with up to
2" (50.8mm) of insulation
Model LFLL100XL
Suitable for water heaters with up to
2
1
⁄
2
" (63.5mm) of insulation
Model LFLLL100XL Suitable for water heaters with up to
3" (76mm) of insulation
1
3
⁄
4
" to 3"
ES-LFSL100XL_LFL100XL_LFLL100XL_LFLLL100XL 0940
USA: 815 Chestnut St., No. Andover, MA 01845-6098; www.watts.com