beautypg.com

Watts SS009 User Manual

Series ss009, Lead free, Stainless steel reduced pressure zone assemblies

background image

For Health Hazard Applications

ES-SS009

Job Name –––––––––––––––––––––––––––––––––––––––––––

Contractor ––––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Engineer –––––––––––––––––––––––––––––––––––––––––––––

Contractor’s P.O. No. –––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Representative ––––––––––––––––––––––––––––––––––––––––

SS009QT

Series SS009

Stainless Steel Reduced Pressure
Zone Assemblies

Sizes:

1

4

" – 1" (8 – 25mm)

Series SS009QT Stainless Steel Reduced Pressure Zone
Assemblies provide protection of the potable water supply in accor-
dance with national plumbing codes and water authority require-
ments. Series SS009 can be used in a variety of health hazard
installations whenever the downstream liquid is of a composition
which may damage bronze material or it is desirable to eliminate
trace elements of lead and copper. Typical applications are:
Industrial or plant use, medical/diagnostic equipment, reverse
osmosis systems, carbonated beverage machines, breweries/dis-
tillers, paper and pulp industry, chemical plants and aggressive
atmospheres. The SS009 series features two in-line independent
check valves, captured springs, replaceable check seats, corrosion
resistant internal parts and a hydraulically operated differential pres-
sure relief valve. All sizes are constructed with NPT body connec-
tions and are standardly furnished with vandal resistant EZ-TC Test
Cocks. Series SS009QT's are furnished with 316 Stainless Steel,
full port, investment cast, quarter turn ball valve shutoffs with 304
Stainless Steel tee handles.

Features

• Investment Cast 316 Stainless Steel Assembly

for corrosion resistance

• All wetted valve components — test cocks, ball valve

shutoffs, pipe nipples, body and cover, check modules and relief
valve assembly are made from "Lead Free" Stainless Steel or
Plastic construction

• Bolted on, top entry single access cover for ease

of maintenance

• Modular check construction featuring nonreversible checks with

captured springs for simplified servicing

• Top mounted vandal resistant EZ-TC test cocks provide easy

access for testing

• Stainless Steel EZ-TC test cocks include dust covers to protect

the threads from dirt, dust and insects

• EZ-TC Test cocks eliminate the need for tools and test fittings
• True line sized check modules open further allowing dirt and debris to

pass freely through the valve reducing fouling problems

• Check and Relief Valve Seats are replaceable without the use of

special tools

• Internal relief valve for right and left hand installations

Specifications

A reduced pressure zone assembly shall be installed at each noted
potential health hazard location to prevent backflow due to back-
siphonage and/or backpressure. The assembly shall consist of an
internal pressure differential relief valve located in a zone between
two independently operating positive seating check modules with
captured springs and silicone seat discs. Seats and seat discs shall
be replaceable in both check modules and the relief valve, without
the use of special tools. There shall be no threads or screws, in the
waterway, exposed to line fluids. Service of all internal components
shall be through a single access cover secured with stainless steel
bolts. The assembly shall include two resilient seated isolation
valves, four top mounted vandal resistant test cocks with dust cov-
ers, a protective stainless steel wye strainer with a 20 mesh screen
and an air gap fitting. The assembly shall consist of an investment
cast 316 Stainless Steel body and cover with Series 300 Stainless
Steel test cocks, 316 Stainless Steel Ball Valve Shutoffs with PTFE
Seat blowout proof 304 Stainless Steel Stems, and 304 Stainless
Steel Tee Handles. The assembly shall meet the requirements of
ASSE Standard 1013, AWWA Standard C511. Assembly shall be a
Watts Regulator Company Series SS009QT.

Test Cock No. 3

Test Cock No. 4

R.P. Zone

Water Outlet

Test Cock
No. 2

First Check
Module
Assembly

Second

Check

Module

Assembly

Relief Valve Assembly

EZ-TC-SS
Test Cocks

Now Available

WattsBox Insulated Enclosures.

For more information, send for literature ES-WB.

LEAD FREE

*

*The wetted surface of this product contacted by consumable water

contains less than one quarter of one percent (0.25%) of lead by weight.

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

ES-SS009.qxd 11/3/09 8:47 AM Page 1