Stainless Series
S114-2 or S6114-2 (Globe)
S1114-2 or S61114-2 (Angle)
Installation Guidelines
• Prior to installation, flush line to remove debris.
• Install valve horizontally “in line” (cover facing UP), so flow arrow matches flow through the line. Avoid
installing valves 6” or large vertically. Consult factory prior to ordering if installation is other than
described.
• Install inlet and outlet isolation valves. NOTE: When using butterfly valves, insure disc does not contact
control valve. Damage or improper valve seating may occur.
• Provide adequate clearance for valve servicing and maintenance.
• Install pressure gauges to monitor valve inlet and outlet pressure.
• Install Orifice Plate Assembly (provided) 3 to 5 pipe diameters downstream of the Rate-of-Flow Valve
with the sensing connections offset from top of pipeline to avoid air accumulation. The Orifice Plate
Assembly should not be installed next to a butterfly valve.
• Connect Orifice Plate Assembly to Rate-of-Flow Pilot using 3/8” diameter minimum copper tubing (field
installed) in accordance with factory piping schematic.
Other Watts ACV Rate-of-Flow Control Valves
S114 / S6114
Rate-of-Flow Control Valve
S114-1 / S6114-1
Rate-of-Flow Control Valve with Solenoid (On-Off) Feature
S114-3 / S6114-3
Rate-of-Flow Control Valve with Hydraulic Check Feature
S114-8 / S6114-8
Rate-of-Flow Control Valve with Pressure Sustaining Feature
RATE-OF-FLOW VALVE with