The Solenoid Control Valve shall be a pilot operated diaphragm valve designed to open fully or close drip-

tight as commanded by a 3-Way Solenoid Pilot. The valve shall have provisions for manual operation in

the event of power outage. Solenoid voltage shall be _________ and enclosure shall be NEMA 4 General

Purpose. The main valve shall (open / close) when the solenoid is energized.

The main valve shall be a hydraulically operated, single diaphragm actuated, globe or angle pattern valve.

Y-pattern valves shall not be permitted. The valve shall contain a disc and diaphragm assembly that forms

a sealed chamber below the valve cover, separating operating pressure from line pressure. The diaphragm

shall be constructed of nylon reinforced Buna-N, and shall not seal directly against the valve seat and shall

be fully supported by the valve body and cover. Rolling diaphragm construction will not be allowed and there

shall be no pistons operating the main valve or any pilot controls.

The main valve body and cover shall be Ductile Iron ASTM A536, and all internal cast components shall be

Ductile Iron or CF8M (316) Stainless Steel. All Ductile Iron components, including the body and cover, shall

be lined and coated with an NSF and FDA Approved Epoxy Coating applied by the electrostatic heat fusion

process. All main valve trim and throttling components (cover bearing, valve seat and disc guide) shall

be Stainless Steel. The valve body and cover must be machined with a 360-degree locating lip to assure

proper alignment.

The disc and diaphragm assembly shall contain a Buna-N synthetic rubber disc with a rectangular cross-

section that is securely retained on 3-1/2 sides by a disc retainer and disc guide. Diaphragm assemblies

utilizing bolts or cap screws for component retention will not be permitted.

The exposed portion of the seat disc shall contact the valve seat and seal drip-tight. The disc and diaphragm

assembly must be guided by two separate bearings, one installed in the valve cover and one concentrically

located within the valve seat, to avoid deflection and assure positive disc-to-seat contact. Center guided

valves will not be permitted. All necessary repairs shall be made from the top of the valve while the body

remains in line.

Pilot control systems for valves 3” and smaller shall contain a Flow Clean Strainer and a 3-Way Solenoid

Pilot with screw type Manual Operator. Pilot control systems for 4” valves shall contain a 3-Way Solenoid

Pilot with screw type Manual Operator, an external Y-Strainer and Isolation Ball Valves on all body connec-

tions. All pilot control systems shall utilize copper tubing and brass fittings regardless of valve size.

The valve shall be Watts ACV Model M113-12 (Globe) or M1113-12 (Angle) Solenoid On-Off Control Valve.