RO System Troubleshooting

PRoblem

coRRective action

General

high Product Water tDs

Membrane expanded.

Replace membrane.

Membrane attack by chlorine

Carbon pre-filter may be exhausted. Replace with a new cartridge.

Clogged pre-filter-creates pressure drop and low reject flow.

Replace pre-filter cartridge.

Feed pressure too low.

Feed pressure must be at least 20psi.

Insufficiently flushed post-filter cartridge.

Flush post-filter with pure water.

Brine seal on membrane leaks.

Determine if seal or o-ring is bad. Replace as needed.

no Product Water or not enough Product Water

Feed water shut off.

Turn on feed water.

Low feed pressure. Feed pressure must be at least 20psi.

Consider booster pump.

Pre-filter cartridge clogged.

Replace pre-filter cartridge.

Membrane fouled.

Determine and correct cause; replace membrane.

Product check valve stuck.

Replace check valve fitting.

Low pump discharge pressure

Open pump discharge valve, replace pump

item numbeR

DescRiPtion

QuantitY PeR sYstem

PWR80243085

PWR80243125

PWR80243165

PWR80243205

1

Pre filter housing 7 round 40"

1

1

1

1

2

Pressure Gauge, 2 1/2", 0-100 psi, LF, Back Mount

2

2

2

2

3

Pressure Gauge, 2 1/2", 0-400 psi, LF, Back Mount

3

3

3

3

4

Flow Meter 2 - 20 gpm

1

1

5

Flow Meter 4 – 40 gpm

1

1

6

Flow Meter 6 - 60 gpm

2

1

7

Flow Meter 10 - 80 gpm

1

1

1

8

Flow Meter 15-130 gpm

1

1

9

Controller with conductivity meter (optional)

1

1

1

1

10

Pump & Motor, 3-Phase, 60Hz, 15 hp

1

11

Pump & Motor, 3-Phase, 60Hz, 20 hp

1

12

Pump & Motor, 3-Phase, 60Hz, 25 hp

1

13

Pump & Motor, 3-Phase, 60Hz, 30 hp

1

14

Low Pressure Switch

1

1

1

1

15

Inlet Solenoid Valve 24 volt, 2”

1

16

Inlet Solenoid Valve 24 volt, 3”

1

1

1

17

RO Membranes

8

12

16

20

18

Pre Filter Cartridges 40” 5 micron

7

7

7

7

IV. Replacement Parts List