Watts FBVS-3C User Manual
Series fbv-3c, fbvs-3c, Piece, full port, brass ball valves, For commercial and industrial applications
![background image](/manuals/589903/1/background.png)
Sizes:
1
/
4
" – 4" (8 – 100mm)
Series FBV-3C 2-piece, full port, brass ball valves are used in com-
mercial and industrial applications for a full range of liquids and
gases. They feature a bottom-loaded blowout proof stem, virgin
PTFE seats, thrust washer, and adjustable stem packing gland, stem
packing nut, chrome plated brass ball, brass adapter, and steel
handle.
Features
• CSA approved threaded valves only
1
/
4
" – 3" (15 – 80mm)
• UL/FM approved threaded valves
1
/
2
" – 2" (15 – 50mm)
• UL Listed solder valves
1
/
2
" – 2" (15 – 50mm)
• Fluorocarbon elastomer stem O-ring prevents stem leaks
• Adjustable stem packing gland
• PTFE stem packing seal, thrust washer, and seats
• Bottom loaded blowout proof stem
• Machined chrome plated brass ball
• Valves comply to MSS-SP-110 standard
• Recommended for open/close applications
Models
FBV-3C:
1
/
4
" – 4" (8 – 100mm) with threaded connections
FBVS-3C:
1
/
2
" – 3" (15 – 80mm) with solder connections
Pressure – Temperature
Water Temperature Range: -40ºF to 400ºF (-40ºC to 204ºC)
Pressure Ratings
FBV-3C :
1
/
4
" – 2" (8 – 50mm)
600psi (41 bar) WOG, non-shock
150psi (10.3 bar) WSP
2
1
/
2
" – 4" (65 – 100mm)
400psi (27.5 bar) WOG, non-shock
125psi (8.6 bar) WSP
FBVS-3C :
1
/
2
" – 2" (15 – 50mm)
600psi (41 bar) WOG, non-shock
150psi (10.3 bar) WSP
2
1
/
2
" – 3" (65 – 80mm)
400psi (27.5 bar) WOG, non-shock
125psi (8.6 bar) WSP
*This valve is designed to be soft soldered into lines without
disassembly, using a low temperature solder to 420°F (216°C).
Higher temperature solders may damage the seat material.
NOTICE
Apply heat with the flame directed
AWAY from the center of the
valve body. Excessive heat can harm the seats. After soldering,
the packing nut may have to be tightened.
Approvals
1
/
2
" – 2" (15 – 50mm) FBV-3C UL/FM approved
1
/
2
" – 2" (15 – 50mm) FBVS-3C UL Listed
Gas Approvals (Threaded Valves Only)
1
/
4
" –
3
/
8
" (8 – 10mm)
ASME B16.33, CSA
ASME B16.44
1
/
2
psig, 5psig, (14, 34 kPa) @ -40ºF to 125ºF (-40ºC to 52ºC)
1
/
2
" – 2" (15 – 50mm)
ASME B16.33, CSA
ASME B16.44
1
/
2
psig, 5psig, and 125psig (14, 34 and 862 kPa)
@ -40ºF to 125ºF (-40ºC to 52ºC)
2
1
/
2
" – 3" (65 – 80mm)
ASME B16.38, CSA
ASME B16.44
1
/
2
psig, 5psig, and 125psig (14, 34 and 862 kPa)
@ -40ºF to 125ºF (-40ºC to 52ºC)
Specifications
Approved valves shall be 2-piece full port design constructed of
a forged brass body and end adapter. Seats and stem packing shall be
virgin PTFE. Stem shall be bottom loaded, blowout proof design with
fluorocarbon elastomer O-ring to prevent stem leaks. Valve shall have
chrome plated brass ball and adjustable packing gland. Threaded valves
1
/
2
" – 3" (shall be CSA approved to
1
/
2
, 5, and 125psig (14, 34 and 862
kPa), UL/FM approved. Solder valves to be UL listed. Valve sizes
1
/
4
" – 2"
(8 – 80mm) shall be rated to 600psi (41 bar) WOG non-shock and 150psi
(10.3 bar) WSP. Valve sizes 2
1
/
2
" – 4" (65 – 100mm) threaded, shall be
rated to 400psi (27.5 bar) WOG non-shock and 125psi (8.6 bar) WSP.
Valve sizes 2
1
/
2
" – 3" (65 – 88mm) solder shall be rated to 400psi (27.5
bar) WOG non-shock and 125psi (8.6 bar) WSP. Valve shall be a Watts
Series FBV-3C (threaded) or FBVS-3C (solder).
For Commercial and Industrial Applications
ES-FBV-3C
Job Name –––––––––––––––––––––––––––––––––––––––––––
Contractor ––––––––––––––––––––––––––––––––––––––––––––
Job Location –––––––––––––––––––––––––––––––––––––––––
Approval –––––––––––––––––––––––––––––––––––––––––––––
Engineer –––––––––––––––––––––––––––––––––––––––––––––
Contractor’s P.O. No. ––––––––––––––––––––––––––––––––––
Approval –––––––––––––––––––––––––––––––––––––––––––––
Representative ––––––––––––––––––––––––––––––––––––––––
FBV-3C
FBVS-3C*
Series FBV-3C, FBVS-3C
approved
2-Piece, Full Port, Brass Ball Valves
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
The information contained herein is not intended to replace the full
product installation and safety information available or the experience
of a trained product installer. You are required to thoroughly read all
installation instructions and product safety information before beginning
the installation of this product.