Watts LF009 User Manual

Series lf009, Lead free, Reduced pressure zone assemblies

background image

LF009

ES-LF009

Series LF009

Reduced Pressure Zone Assemblies

Sizes:

1

4

" – 3" (8 – 80mm)

Series LF009 Reduced Pressure Zone Assemblies are designed to

protect potable water supplies in accordance with national plumbing

codes and water authority requirements. This series can be used in a

variety of installations, including the prevention of health hazard cross-

connections in piping systems or for containment at the service line

entrance.The LF009 features Lead Free* construction to comply with

Lead Free* installation requirements.
This series features two in-line, independent check valves, captured

springs and replaceable check seats with an intermediate relief valve.

Its compact modular design facilitates easy maintenance and assem-

bly access. Sizes

1

4

" – 1" (8 – 25mm) shutoffs have tee handles.

Features

Single access cover and modular check construction

for ease of maintenance

• Top entry - all internals immediately accessible
• Captured springs for safe maintenance
• Internal relief valve for reduced installation clearances
• Replaceable seats for economical repair
• Lead Free* cast copper silicon alloy body construction for durability

1

4

" – 2" (8 – 50mm)

• Fused epoxy coated cast iron body 2

1

2

" and 3" (65 and 80mm)

• Ball valve test cocks — screwdriver slotted

1

4

" – 2" (8 – 50mm)

• Large body passages provides low pressure drop
• Compact, space saving design
• No special tools required for servicing

Specifications

A Reduced Pressure Zone Assembly shall be installed at each potential

health hazard location to prevent backflow due to backsiphonage and/

or backpressure. The assembly shall consist of an internal pressure

differential relief valve located in a zone between two positive seating

check modules with captured springs and silicone seat discs. Seats and

seat discs shall be replaceable in both check modules and the relief

valve. There shall be no threads or screws in the waterway exposed to

line fluids. Service of all internal components shall be through a single

access cover secured with stainless steel bolts. Body and shutoffs shall

be constructed using Lead Free* cast copper silicon alloy materials.

Lead Free* reduced pressure zone assembly shall comply with state

codes and standards, where applicable, requiring reduced lead content.
The assembly shall also include two resilient seated isolation valves,

four resilient seated test cocks and an air gap drain fitting. The assem-

bly shall meet the requirements of: USC; ASSE Std. 1013; AWWA Std.

C511; CSA B64.4. Shall be a Watts Series LF009.

Test Cock No. 3

Test Cock No. 4

R.P. Zone

Water Outlet

Test Cock

No. 2

First Check

Module

Assembly

Second

Check

Module

Assembly

Relief Valve Assembly

Ball Type

Test Cocks

For Health Hazard Applications

LEAD FREE

*

Job Name –––––––––––––––––––––––––––––––––––––––––––

Contractor ––––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Engineer –––––––––––––––––––––––––––––––––––––––––––––

Contractor’s P.O. No. ––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Representative ––––––––––––––––––––––––––––––––––––––––

*The wetted surface of this product contacted by consumable

water contains less than 0.25% of lead by weight.

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

Now Available

WattsBox Insulated Enclosures.

For more information, send for literature ES-WB.

NOTICE

Inquire with governing authorities for local installation requirements

The information contained herein is not intended to replace the full

product installation and safety information available or the experience

of a trained product installer. You are required to thoroughly read all

installation instructions and product safety information before begin-

ning the installation of this product.