Headloss

Flow Rate - Gallons per minute (Water)

Pressure Drop (psi)

Angle
Globe

2

4

6 8 10

20

40

60 80 100

200

500

1000

2000

5000

10000

20000

100

80

60

40

30

20

10

8

6

4

3

2

Maximum continuous flow based on velocity of 20 ft. per second.
Maximum intermittent flow based on velocity of 25 ft. per second.
The C

v

Factor of a value is the flow rate in US GPM at 60°F that will cause a 1psi drop in pressure.

The factors stated are based upon a fully open valve.
C

v

factor can be used in the following equations to determine Flow (Q) and Pressure Drop (∆P):

Q (Flow) = C

v

√∆P ∆P (Pressure Drop) = (Q/C

v

)

2

ES-ACV-M400-M1400 1219

© 2012 Watts

USA: Tel. (713) 943-0688 • (713) 944-9445 • www.watts.com

A Watts Water Technologies Company

M400 / M1400 — Full Port Ductile Iron Single Chamber Basic Valve with
Mechanical Check Feature

Flow Data - ACV M400 (Globe) / M1400 (Angle)

Valve Size - Inches

3

4

6

8

10

12

14

16

Maximum Continuous

Flow Rate Gpm (Water)

485

800

1850

3100

5000

7000

8500

11100

Maximum Intermittent

Flow Rate Gpm (Water)

590

1000

2300

4000

6250

8900

10800

14100

C

V

Factor GPM (Globe)

100

175

490

770

1200

1750

2125

2890

C

V

Factor GPM (Angle)

125

215

571

990

1530

2525

2885

3575

Estimated

Valve Cover Chamber Capacity

Valve Size - Inches

3

4

6

8

10

12

14

16

fluid oz.

16

22

70

U.S. Gal

1-1/4

2-1/2

4

6-1/2

9-1/2

Valve Travel

Valve Size - Inches

3

4

6

8

10

12

14

16

Travel - Inches

3/4

1

1-1/2

2

2-1/2

3

3-1/2

4

4

3

10

6

8

12 14 16

4

3

10

6

8

12 14 16