Headloss, Valve cover chamber capacity, Valve travel – Watts M400 / M1400 User Manual
Page 2

Headloss
Flow Rate - Gallons per minute (Water)
Pressure Drop (psi)
Angle
Globe
2
4
6 8 10
20
40
60 80 100
200
500
1000
2000
5000
10000
20000
100
80
60
40
30
20
10
8
6
4
3
2
Maximum continuous flow based on velocity of 20 ft. per second.
Maximum intermittent flow based on velocity of 25 ft. per second.
The C
v
Factor of a value is the flow rate in US GPM at 60°F that will cause a 1psi drop in pressure.
The factors stated are based upon a fully open valve.
C
v
factor can be used in the following equations to determine Flow (Q) and Pressure Drop (∆P):
Q (Flow) = C
v
√∆P ∆P (Pressure Drop) = (Q/C
v
)
2
ES-ACV-M400-M1400 1219
© 2012 Watts
USA: Tel. (713) 943-0688 • (713) 944-9445 • www.watts.com
A Watts Water Technologies Company
M400 / M1400 — Full Port Ductile Iron Single Chamber Basic Valve with
Mechanical Check Feature
Flow Data - ACV M400 (Globe) / M1400 (Angle)
Valve Size - Inches
3
4
6
8
10
12
14
16
Maximum Continuous
Flow Rate Gpm (Water)
485
800
1850
3100
5000
7000
8500
11100
Maximum Intermittent
Flow Rate Gpm (Water)
590
1000
2300
4000
6250
8900
10800
14100
C
V
Factor GPM (Globe)
100
175
490
770
1200
1750
2125
2890
C
V
Factor GPM (Angle)
125
215
571
990
1530
2525
2885
3575
Estimated
Valve Cover Chamber Capacity
Valve Size - Inches
3
4
6
8
10
12
14
16
fluid oz.
16
22
70
U.S. Gal
1-1/4
2-1/2
4
6-1/2
9-1/2
Valve Travel
Valve Size - Inches
3
4
6
8
10
12
14
16
Travel - Inches
3/4
1
1-1/2
2
2-1/2
3
3-1/2
4
4
3
10
6
8
12 14 16
4
3
10
6
8
12 14 16