Valve cover chamber capacity valve travel headloss – Watts F1513-6 User Manual
Page 2

Flow Rate - Gallons per minute (Water)
Pressure Drop (p.s.i.)
Angle
Globe
2 4 6 8
10
20
40
60 80 100 200 500 1000 2000 5000 10000 20000
100,000
100
80
60
40
30
20
10
8
6
4
3
2
Maximum continuous flow based on velocity of 20 ft. per second.
Maximum intermittent flow based on velocity of 25 ft. per second.
The C
V
factor of a valve is the flow rate in US GPM at 60° F that will cause a 1 psi drop in pressure.
The factors stated are based upon a fully open valve.
C
V
factor can be used in the following equations to determine Flow (Q) and Pressure Drop (
r P):
Q (Flow) = C
V
r P
rP (Pressure Drop) = (Q/C
V
)
2
Valve Size - Inches
2
2-1/2
3
4
6
8
10
12
14
16
Maximum Continuous
Flow Rate Gpm (Water)
208
300
460
800
1800
3100
4900
7000
8500
11000
Maximum Intermittent
Flow Rate Gpm (Water)
260
370
570
1000
2300
3900
6000
8600
10500
14000
CV Factor GPM (Globe)
55
75
125
220
460
775
1200
1730
2100
2800
CV Factor GPM (Angle)
66
99
170
280
650
1100
1600
2500
3060
4210
Estimated
Valve Size (in)
2
2-1/2
3
4
6
8
10
12
14
16
fl.oz.
4
10
10
22
70
U.S. Gal
1-1/4
2-1/2
4
6-1/2
9-1/2
Valve Size (in)
2
2-1/2
3
4
6
8
10
12
14
16
Travel (in)
1/2
5/8
3/4
1
1-1/2
2
2-1/2
3
3-1/2
4
Flow Data - ACV F500 (Globe) / F1500 (Angle)
2-1/2
4
10
6
8
2
3
12 14 16
2-1/2
4
10
6
8
2
3
12 14
16
Valve Cover Chamber Capacity
Valve Travel
Headloss
8550 Hansen Road
•
Houston, Texas 77075
•
(Ph) 713.943.0688
•
(Fx) 713.944.9445
•
www.wattsacv.com