Figure 2 radiant heat application, Figure 3 temperature adjustment, Quick-connect installation – Watts LFL1170 User Manual

Page 2: Figure 1 domestic hot water application, Notice

background image

Figure 2

Radiant Heat Application

from Boiler

Cold

Radiant Return

Mixed

to Radiant

to Boiler

Watts Flow

Check

Watts

Ball Valve

TP

Test Plug

Watts

Ball Valve

RPV

CV, CVS

Check Valve

Circulator

LF1170-M2,

LFL1170-M2

Hotter

3

/

32

" Hex Wrench

Turn

Colder

Unscrew, lift

cap to adjust

Figure 3
Temperature Adjustment

Factory Preset:

LF1170-M2: 120°F (49°C)

LFL1170-M2: 90°F (31°C)

Under following conditions:

Cold Inlet: 60-70°F (16-21°C)

Hot Inlet: 140-145°F (60-63°C)

Supply Pressure: 45psi (3.15 bar)

1. Let water flow for at least two minutes to allow supply tem-

perature to stabilize.

2. Calibrate the mixed water outlet temperature by placing a

thermometer in the mixed water stream.

3. To adjust the setting of the valve, loosen locking cap screw

with hex wrench, see Figure 3. Cap must be lifted 1/4" to

adjust temperature. To increase the temperature, turn coun-

terclockwise. To decrease temperature turn clockwise.

4. Lower handle and tighten screw.
5. Check outlet temperature.

Quick-Connect Installation

1. Mark pipe as shown.

This is pipe insertion depth.

2. Clean pipe end.

1. Remove collet clip.

2. Depress collet.

3. Pull tubing from tailpiece.

3. If using PEX tubing, insert pipe

stiffener (provided) into end of pipe.

4. Push tubing into tailpiece up to mark.

5. Insert collet clip.

To Connect

To Disconnect

PEX tubing only

Pipe Stiffener

Tail Piece

Mark

Collet clip

Collet depressed

1

1

/

2

in. (38.1mm)

1

3

/

4

in. (44.45mm)

1

7

/

8

in. (47.63mm)

3

/

4

in.Pipe (19.05mm)

1 in.Pipe (25.4mm)

1

/

2

in.Pipe (12.7mm)

Figure 1
Domestic Hot Water Application

Watts

Vacuum Relief

Valve

Watts Temperature

Gauge

Cold

Cold

Cold

LF1170-M2 or

LFL1170-M2

Tempered

Hot

Hot to

Appliances

Watts T&P

Relief Valve

*8" – 12"

H
C

M

Domestic Hot Water Application

NOTICE

To prolong the life of the valve, it is recommended the valve

be trapped as shown
Devices tested to ASSE 1016, ASSE 1070 or ASSE 1069

such as Watts LFUSG, LFL111 or LFMMV should be used

at fixture to prevent possible injury.