beautypg.com

Watts S1113-40 User Manual

Stainless series, Electronic control valve, For electric valve positioning)

background image

8550 Hansen Road

Houston, Texas 77075

(Ph) 713.943.0688

(Fx) 713.944.9445

www.wattsacv.com

01/05

R

Stainless Series

ELECTRONIC CONTROL VALVE

(for Electric Valve Positioning)

S113-40 or S6113-40 (Globe)

S1113-40 or S61113-40 (Angle)

Operation

The Watts ACV Electronic Control Valve is designed to be electrically positioned to control flow, pressure,
level or temperature for water applications. It is a throttling valve controlled by two 2-way solenoids installed
in the pilot control system, one connecting the valve cover chamber with upstream pressure and the other
connecting the main valve cover chamber downstream. By alternately energizing the solenoids, line pressure
is admitted to or relieved from the cover chamber of the main valve, allowing the valve to be “positioned” to
maintain a desired value.

The valve is normally interfaced with SCADA systems or a Programmable Logic Controller that compares a
Process Variable (PV) to a desired setpoint, and energizes the solenoid pilots to throttle the valve open or
closed until the PV reaches the desired setpoint.

Rate of valve operation is controlled by separate adjustable Opening and Closing Speed Controls that
control the rate fluid and pressure are admitted to or relieved from the main valve cover chamber.

The valve is constructed with two “normally closed” solenoids allowing the valve to “hold last position”
upon power failure. The valve may also be configured to open fully or close drip tight upon power failure if
desired.

Specify valve to “hold last position”, “open fully” or “close drip tight” upon power failure prior to
ordering.

Installation Guidelines

• Prior to installation, flush line to remove debris.
• Install valve horizontally “in line” (cover facing UP), so flow arrow matches flow through the line. Avoid

installing valves 6” and larger vertically. Consult factory prior to ordering if installation is other than
described.

• Install inlet and outlet isolation valves. NOTE: When using butterfly valves, insure disc does not contact

control valve. Damage or improper valve seating may occur.

• Provide adequate clearance for valve servicing and maintenance.
• Install pressure gauges to monitor valve inlet and outlet pressure.
• Connect Solenoid Pilots to appropriate power source in compliance with local electrical codes.

Other Watts ACV Solenoid Control Valves

S113-12 / S6113-12

Solenoid (On-Off) Valve (4” & smaller)

S113-6 / S6113-6

Solenoid (On-Off) Valve (6” & larger)

S113-25 / S6113-25

Solenoid (On-Off) Valve with Hydraulic Check Feature (4” & smaller)

S113-32 / S6113-32

Solenoid (On-Off) Valve with Hydraulic Check Feature (6” & larger)

This manual is related to the following products: