Flow Rate - Gallons per minute (Water)

Pressure Drop (p.s.i.)

Angle
Globe

2 4 6 8

10

20

40

60 80 100 200 500 1000 2000 5000 10000 20000

100,000

100

80

60

40

30

20

10

8

6

4

3

2

Maximum continuous flow based on velocity of 20 ft. per second.
Maximum intermittent flow based on velocity of 25 ft. per second.
The C

V

factor of a valve is the flow rate in US GPM at 60° F that will cause a 1 psi drop in pressure.

The factors stated are based upon a fully open valve.
C

V

factor can be used in the following equations to determine Flow (Q) and Pressure Drop (

r P):

Q (Flow) = C

V

r P

rP (Pressure Drop) = (Q/C

V

)

2

Valve Size - Inches

1-1/4

1-1/2

2

2-1/2

3

4

6

8

10

12

14

16

Maximum Continuous

Flow Rate Gpm (Water)

93

125

208

300

460

800

1800

3100

4900

7000

8500

11000

Maximum Intermittent

Flow Rate Gpm (Water)

115

158

260

370

570

1000

2300

3900

6000

8600

10500 14000

CV Factor GPM (Globe)

29

34

55

75

125

220

460

775

1200

1730

2100

2800

CV Factor GPM (Angle)

39

53

66

99

170

280

650

1100

1600

2500

3060

4210

Estimated

Valve Cover Chamber Capacity

Valve Size (in)

1-1/4

1-1/2

2

2-1/2

3

4

6

8

10

12

14

16

fl.oz.

4

4

4

10

10

22

70

U.S. Gal

1-1/4

2-1/2

4

6-1/2

9-1/2

Valve Travel

Valve Size (in)

1-1/4

1-1/2

2

2-1/2

3

4

6

8

10

12

14

16

Travel (in)

3/8

3/8

1/2

5/8

3/4

1

1-1/2

2

2-1/2

3

3-1/2

4

Flow Data - ACV F100 (Globe) / F1100 (Angle)

2-1/2

4

10

6

8

2

3

12 14 16

2-1/2

4

10

6

8

2 3

12 14 16

1-1/4 1-1/2

1-1/4 1-1/2

Valve Cover Chamber Capacity

Valve Travel

Headloss

8550 Hansen Road

Houston, Texas 77075

(Ph) 713.943.0688

(Fx) 713.944.9445