beautypg.com

Dimensions - weights, Specifications, Feed water guidelines – Watts PWR4024 User Manual

Page 2: Performance, Ordering information

background image

Dimensions - Weights

FRONT

SIDE

C

FRONT

FRONT

SIDE

B

A

SIDE

Specifications

Watts Pure Water Series PWR4024 reverse osmosis system shall

be installed to provide reverse osmosis quality water. The RO

system shall be installed after a Series PWS water softener so that

scale forming calcium and magnesium hardness cannot scale the

RO membrane. Series PWC backwashing carbon filter shall be

installed on the RO feed water line to remove chlorine and prevent

membrane degradation due to chlorine attack. Series PWM back-

washing sediment filter shall also be installed on the RO feed water

line to reduce the silt density index of the water to prevent particu-

late fouling of the RO membrane.
The RO system shall be a high-pressure/high-rejection type unit

complete with permeate and reject water flow meters, reject recy-

cle water flow meter, pre-filter inlet and outlet pressure gauges,

membrane feed and reject water pressure gauges, FRP mem-

brane housings, automatic inlet diaphragm valve, low feed water

pressure switch, reject and recycle valves, digital controller with

conductivity meter and high-conductivity alarm output, storage

tank level and pretreatment interlock inputs, 10 horse power mul-

tistage centrifugal high-pressure pump, and all other components

necessary for proper operation. The system shall be a floor mount

design. The RO permeate water shall be collected in an atmo-

spheric storage tank with the tank level controlled by an electronic

level float. The RO shall be equipped with inputs for the tank level

float as well as pretreatment interlock to shut the RO system down

in the event the pretreatment begins a backwash cycle. Electrical

requirements are 230 volt 60 hertz three phase. A local drain is

required to accept drain water from the system. The feed water

pressure must not fall below 20psi. The feed water temperature

must not fall below 35°F or exceed 100°F (2-39°C).
The system shall produce reverse osmosis quality water with 97

percent minimum average ionic rejection of total dissolved solids

when operated within the manufacturer’s operational specifications.

Feed Water Guidelines

pH . . . . . . . . . . . . . . . . . . . . . . 6 to 9
Hardness (maximum) . . . . . . . Less than 1 grain per gallon as

CaCO3 (Softened) or anti scale

chemical injection if not softened

(contact your Watts representative)

Feed Water Pressure (minimum) .20psi
Temperature . . . . . . . . . . . . . . . 35 - 100°F (2 - 38°C)
Free Chlorine (maximum) . . . . . None Allowed
Iron (maximum) . . . . . . . . . . . . . Less than .1mg/L
Oil and H2S . . . . . . . . . . . . . . . None Allowed
Turbidity . . . . . . . . . . . . . . . . . Less than 1.0 NTU
Silt Density Index . . . . . . . . . . . Less than 5.0 SDI

Notes:
* For all other guideline information please contact your Watts representative.
* Published maximum production rates are based on a feed water of 77°F, SDI

of less than 3, 1000 ppm TDS, and pH 8. Individual membrane productivity may

vary (± 15%). May be operated on other feed waters with reduced capacity.

* Percent rejection is based on membrane manufacturer’s specifications; overall

system percent rejection may be less.

MODEl NO.

DIMENSIONS

WEIGHTS

A B C

in. mm in. mm in. mm lbs kgs

PWR40243163 26 660 74 1880 186 4724 1400 636
PWR40243203 26 660 74 1880 186 4724 1600 727
PWR40243243 26 660 74 1880 186 4724 1800 818

Maximum Productivity (gallons per minute)

20

25

30

Quality (typical membrane percent rejection)

98%

Recovery (adjustable)

65% – 75%

Membrane Size

4" x 40"

Membrane Array (four elements per vessel)

2:2

3:2

4:2

Prefilter
(system ships with five micron cartridges)

7 round x 20"

Feed Water Connection

2" Flange

Product Water Connection

1.5" Flange

Reject Water Connection

1" Flange

Feed Water Required (GPM at 65% recovery)

31

39

46

Minimum Feed Water Pressure

20 psig

Drain Required (maximum)

31

39

46

Electrical Requirement
(other voltages available)

230 VAC, 3-phase,

60 Hz, 30 amps

Motor Horse Power / Type

10 / TEFC

Dimensions L x W x H (approximate)

192" x 26" x 72"

Shipping Weight (estimated pounds)

1400

1600

1800

Performance

Model No.

Description

PWR40243163

20 GPM Reverse Osmosis System with Micro Processor
Controller and Auto Flush

PWR40243203

25 GPM Reverse Osmosis System with Micro Processor
Controller and Auto Flush

PWR40243243

30 GPM Reverse Osmosis System with Micro Processor
Controller and Auto Flush

Ordering Information

ES-WQ-PWR4024 1122

© 2011 Watts

USA: North Andover, MA • Tel. (800) 224-1299 • www.watts.com

Canada: Burlington, ON • Tel. (888) 208-8927 • www.wattscanada.ca