Service, Replacement Parts and Maintenance

Series 719 and LF719 Double Check Valve Assemblies

Servicing the First and Second Check Valves

NOTICE

Before servicing, be certain water is turned off or shutoff valves

are closed

1. Close shutoff valves up and downstream of the valve.
2. Using an appropriate sized wrench, loosen the check valve

cover. Unscrew the check valve cover and lift off.

3. Remove spring.
4. Lift out disc holder assembly from body of valve.
5. To reverse the seat disc, unscrew disc screw and disassem-

ble disc washer and disc rubber from disc holder assembly.

Reverse rubber so opposite face is showing. Assemble disc

screw through disc washer and rubber and screw into disc

holder.

6. To replace seat module, pull out of body by gripping at rein-

forcement ring. Replace seat module with new component

by placing into body seat bore. Tightening cover will engage

seat properly.

7. Insert disc holder assembly back into seat module.
8. Replace spring insuring that it seats properly on disc holder.
9. Place cover onto spring with internal guide on cover posi-

tioned inside end coil.

10. Screw cover onto valve body.
11. Tighten cover wrench tight.
10. Open shutoff valves.

Seat

O-ring

Disc Screw

Reinforcement

Ring

Seat

Disc Washer

Disc Rubber

Disc Holder

Cover

Cover

O-Ring

Spring

Body

3