Headloss, Valve cover chamber capacity, Valve travel – Watts S518 / S1518 User Manual
Page 2
Headloss
Flow Rate - Gallons per minute (Water)
Pressure Drop (psi)
Angle
Globe
2
4
6 8 10
20
40
60 80 100
200
500
1000
2000
5000
10000
20000
100
80
60
40
30
20
10
8
6
4
3
2
Maximum continuous flow based on velocity of 20 ft. per second.
Maximum intermittent flow based on velocity of 25 ft. per second.
The C
v
Factor of a value is the flow rate in US GPM at 60°F that will cause a 1psi drop in pressure.
The factors stated are based upon a fully open valve.
C
v
factor can be used in the following equations to determine Flow (Q) and Pressure Drop (∆P):
Q (Flow) = C
v
√∆P ∆P (Pressure Drop) = (Q/C
v
)
2
ES-ACV-S518-S1518 1219
© 2012 Watts
USA: Tel. (713) 943-0688 • (713) 944-9445 • www.watts.com
A Watts Water Technologies Company
S518-S1518 — Full Port Stainless Steel Dual Chamber Basic Valve with
Mechanical Check Feature
Flow Data - ACV S518 (Globe) / S1518 (Angle)
Valve Size - Inches
4
6
8
10
12
16
Maximum Continuous
Flow Rate Gpm (Water)
800
1850
3100
5000
7000
11100
Maximum Intermittent
Flow Rate Gpm (Water)
1000
2300
4000
6250
8900
14100
CV Factor GPM (Globe)
210
460
790
1260
1725
2940
CV Factor GPM (Angle)
250
561
990
1590
2500
4200
Estimated
Valve Cover Chamber Capacity
Valve Size - Inches
4
6
8
10
12
16
fluid oz.
22
70
U.S. Gal
1-1/4
2-1/2
4
9-1/2
Valve Travel
Valve Size - Inches
4
6
8
10
12
16
Travel - Inches
1
1-1/2
2
2-1/2
3
4
4
6
8
10 12
16
4
6
8
10
12
16