Flow Rate - Gallons per minute (Water)

Pressure Drop (p.s.i.)

Angle
Globe

2 4 6 8

10

20

40

60 80 100 200 500 1000 2000 5000 10000 20000

100,000

100

80

60

40

30

20

10

8

6

4

3

2

Maximum continuous flow based on velocity of 20 ft. per second.
Maximum intermittent flow based on velocity of 25 ft. per second.
The C

V

factor of a valve is the flow rate in US GPM at 60° F that will cause a 1 psi drop in pressure.

The factors stated are based upon a fully open valve.
C

V

factor can be used in the following equations to determine Flow (Q) and Pressure Drop (

r P):

Q (Flow) = C

V

r P

rP (Pressure Drop) = (Q/C

V

)

2

Valve Cover Chamber Capacity

Valve Size (in)

2

2-1/2

3

4

6

8

10

12

14

16

fl.oz.

4

10

10

22

70

U.S. Gal

1-1/4

2-1/2

4

6-1/2

9-1/2

Valve Size - Inches

2

2-1/2

3

4

6

8

10

12

14

16

Maximum Continuous

Flow Rate Gpm (Water)

210

300

485

800

1850

3100

5000

7000

8500

11100

Maximum Intermittent

Flow Rate Gpm (Water)

265

390

590

1000

2300

4000

6250

8900

10800

14100

C

V

Factor GPM (Globe)

45

75

100

175

490

770

1200

1750

2125

2890

C

V

Factor GPM (Angle)

57

91

125

215

571

990

1530

2525

2885

3575

Estimated

Valve Travel

Valve Size (in)

2

2-1/2

3

4

6

8

10

12

14

16

Travel (in)

1/2

5/8

3/4

1

1-1/2

2

2-1/2

3

3-1/2

4

Flow Data - ACV M500 (Globe) / M1500 (Angle)

2-1/2

4

10

6

8

2

3

12 14

16

2-1/2

4

10

6

8

2

3

12 14 16

Valve Cover Chamber Capacity

Valve Travel

Headloss