beautypg.com

Watts S1118-4 User Manual

Stainless series, Non-surge check valve, 6” and larger)

background image

8550 Hansen Road

Houston, Texas 77075

(Ph) 713.943.0688

(Fx) 713.944.9445

www.wattsacv.com

01/05

R

Stainless Series

NON-SURGE CHECK VALVE

(6” and Larger)

S118-4 or S6118-4 (Globe)

S1118-4 or S61118-4 (Angle)

Operation

The Watts ACV Non-Surge Check Valve is designed to control pipeline surges caused by flow reversal
by slowly opening and closing at separate adjustable rates. The valve opens when upstream pressure is
greater than downstream pressure. When upstream pressure is greater than downstream pressure, the
Adjustable Opening Speed Control allows fluid out of the main valve cover chamber, providing a controlled
rate of opening. When a pressure reversal occurs and downstream pressure becomes higher than upstream
pressure, the two Adjustable Closing Speed Controls allows the higher downstream pressure to enter the
main valve cover chamber, providing a controlled rate of closure.

NOTE: A maximum pipeline velocity of six feet-per-second is recommended when installing this type of
check valve. When pipeline velocities exceed six FPS, consideration should be given to adding a Watts
ACV Model S116 Pressure Relief Valve or Model S116-52 Combination Surge Anticipator and Pressure
Relief Valve to the system.

Installation Guidelines

• Prior to installation, flush line to remove debris.
• Install valve horizontally “in line” (cover facing UP), so flow arrow matches flow through the line. Avoid

installing valves 6” and larger vertically. Consult factory prior to ordering if installation is other than
described.

• Install inlet and outlet isolation valves. NOTE: When using butterfly valves, insure disc does not contact

control valve. Damage or improper valve seating may occur.

• Provide adequate clearance for valve servicing and maintenance.
• Install pressure gauges to monitor valve inlet and outlet pressure.

Other Watts ACV Control Valves

S116 / S6116

Pressure Relief Valve

S116-52 / S6116-52

Surge Anticipator and Pressure Relief Valve

S118-3 / S6118-3

Non-Surge Check Valve (4” & smaller)

S513-5 / S6513-5

Pump Control Valve

S513-AK / S6513-AK Pump Control Valve with High Capacity Pilot System
S513-6 / S6513-6

Deep Well Pump Control Valve

S513-14 / S6513-14

Deep Well Pump Control Valve with Pressure Relief Feature

S113-21 / S6113-21

Pump Control Valve

This manual is related to the following products: