beautypg.com

Mustang series, Pressure relief and surge anticipator valve – Watts M1116-52 User Manual

Page 2

background image

8550 Hansen Road

Houston, Texas 77075

(Ph) 713.943.0688

(Fx) 713.944.9445

www.wattsacv.com

01/05

R

Mustang Series

M116-52 or M6116-52 (Globe)

M1116-52 or M61116-52 (Angle)

Installation Guidelines

• Prior to installation, flush line to remove debris.
• Install valve horizontally “in line” (cover facing up), so flow arrow matches flow through the line. Avoid

installing valves 6” and larger vertically. Consult factory prior to ordering if installation is other than
described.

• Install upstream and outlet isolation valves. NOTE: When using butterfly valves, insure disc does not

contact control valve. Damage or improper valve seating may occur.

• Provide adequate clearance for valve servicing and maintenance.
• Install pressure gauge to monitor discharge header pressure.
• Connect sensing line to main discharge header using 3/4” diameter minimum tubing / piping.

Other Watts ACV Pressure Relief / Backpressure or Sustaining Control Valves

M116 / M6116

Pressure Relief / Backpressure or Sustaining Valve

M116-5 / M6116-5

Backpressure / Sustaining Valve with Hydraulic Check Feature

M116-31 / M6116-31 Pressure Sustaining Valve with Solenoid (On-Off) Feature
M116-32 / M6116-32 Pressure Sustaining Valve with Solenoid (On-Off) and Check Features

PRESSURE RELIEF and
SURGE ANTICIPATOR VALVE

This manual is related to the following products: