Model 6115-7JM Installation
Prior to installation, flush line to remove debris.
1.
Install valve horizontally “in line” (cover facing up), so flow arrow matches flow through the line.
Consult
factory prior to ordering if installation is other than described.
2.
Install inlet and outlet isolation valves.
Note: When using butterfly valves, ensure disc does not contact control valve. Damage or improper valve
seating can occur.
3.
Provide adequate clearance for valve servicing and maintenance.
4.
Install pressure gauges to monitor valve inlet and outlet pressure.
Note:
If installation is subjected to very low flow or potentially static conditions, It is recommended that a
pressure relief valve (1/2" minimum) be installed downstream of the Pressure Reducing Valve for additional
system protection. See Watts Model PV20-CB.
Start-Up Instructions
Note: Set-up the Model 6115-7JM in a flowing condition for proper start-up. Automatic Control Valve start-up
requires bringing the valve into service in a controlled manner. All adjustments to control pilot and speed
controls should be made slowly, allowing the valve to respond and the system to stabilize. For proper
operation, the Surge Control Pilot is adjusted approximately 5 psi higher than the Pressure Reducing Pilot.
1.
Close upstream and downstream isolation valves.
2.
Turn the Reducing Pilot (item 2) adjustment screw counterclockwise, releasing the spring tension. Isolate
the Surge Control Pilot by turning its adjustment screw clockwise. Open all isolation Ball Valves.
3.
Turn Adjustable Opening Speed Control (item 4) clockwise until seated, and then counterclockwise 2-1/2
turns. This is an approximate setting and should be fine tuned to suit system requirements once pressure
adjustments have been made.
4.
Slowly open the upstream isolation valve. Loosen air bleed petcock on Position Indicator (item 5) allowing air
to vent. Close the air bleed petcock when all air is vented.
5.
Slowly open the downstream isolation valve. Gradually turn the Reducing Pilot adjustment screw clockwise
to raise the downstream pressure.
There must be a demand for flow for proper start-up
. Continue to adjust
Reducing Pilot until downstream pressure is approximately 5 psi higher than the desired outlet pressure.
6.
While observing downstream pressure gauge (or position indicator) slowly turn Surge Control Pilot
adjustment screw counterclockwise until downstream pressure quickly falls. The Surge Control Pilot is set
at the point when the Model 6115-7JM begins to close. Tighten the locknut on the Surge Control Pilot. Turn
adjustment screw counterclockwise on Pressure Reducing Pilot, decreasing setpoint, until desired
downstream pressure is achieved. Tighten locknut on Pressure Reducing Pilot.
The Surge Control Pilot is
set approximately 5 psi higher than the reduced pressure setpoint.
7.
Fine tune Opening Speed Control to suit system requirements. Adjust Opening Speed Control clockwise for
slower opening, and counterclockwise for faster opening.