Watts 9 User Manual

Series 009, Reduced pressure zone assemblies, For health hazard applications

background image

For Health Hazard Applications

ES-009

Series 009

Reduced Pressure Zone

Assemblies

Sizes:

1

4

" – 2"

Series 009 Reduced Pressure Zone Assemblies are designed

to protect potable water supplies in accordance with national

plumbing codes and water authority requirements. This series

is designed to protect drinking water supplies from dangerous

cross-connections in accordance with national plumbing codes

and water authority requirements for non-potable service appli-

cations such as irrigation, fireline, or industrial processing.
This series features two in-line, independent check valves, cap-

tured springs and replaceable check seats with an intermediate

relief valve. Its compact modular design facilitates easy main-

tenance and assembly access. Sizes

1

4

" – 1" shutoffs have tee

handles.

Features

• Single access cover and modular check construction

for ease of maintenance

• Top entry - all internals immediately accessible
• Captured springs for safe maintenance
• Internal relief valve for reduced installation clearances
• Replaceable seats for economical repair
• Bronze body construction for durability

1

4

" – 2"

• Ball valve test cocks — screwdriver slotted

1

4

" – 2"

• Large body passages provides low pressure drop
• Compact, space saving design
• No special tools required for servicing

Specifications

A Reduced Pressure Zone Assembly shall be installed at each

potential health hazard location to prevent backflow due to

backsiphonage and/or backpressure. The assembly shall

consist of an internal pressure differential relief valve located

in a zone between two positive seating check modules with

captured springs and silicone seat discs. Seats and seat discs

shall be replaceable in both check modules and the relief valve.

There shall be no threads or screws in the waterway exposed

to line fluids. Service of all internal components shall be through

a single access bronze cover secured with stainless steel bolts.

The assembly shall also include two resilient seated isolation

valves, four resilient seated test cocks and an air gap drain fit-

ting. The assembly shall meet the requirements of: USC; ASSE

Std. 1013; AWWA Std. C511-92; CSA B64.4. Shall be a Watts

Series 009.

† Does not indicate approval status. Refer to Page 2 for

approved sizes & models.

009QT-S

009M2QT

Test Cock No. 3

Test Cock No. 4

R.P. Zone

Water Outlet

Test Cock

No. 2

First Check

Module

Assembly

Second

Check

Module

Assembly

Relief Valve Assembly

Ball Type

Test Cocks

Now Available

WattsBox Insulated Enclosures.

For more information, send for literature ES-WB.

Job Name –––––––––––––––––––––––––––––––––––––––––––

Contractor ––––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Engineer –––––––––––––––––––––––––––––––––––––––––––––

Contractor’s P.O. No. ––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––

Representative ––––––––––––––––––––––––––––––––––––––––

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

NOTICE

Inquire with governing authorities for local installation

requirements