Watts SS007 User Manual

Installation instructions, Double check valve assemblies, Indoors

background image

Installation, Maintenance, & Repair
Series 007 and LF007

Double Check Valve Assemblies

Sizes:

1

2

" – 3" (15 - 80mm)

NOTICE

For Australia and New Zealand, line strainers should be installed

between the upstream shutoff valve and the inlet of the backflow

preventer.

3

4

" 007M3QT

RP/IS-007

Watts product specifications in U.S. customary units and metric

are approximate and are provided for reference only. For precise

measurements, please contact Watts Technical Service. Watts

reserves the right to change or modify product design, construc-

tion, specifications, or materials without prior notice and without

incurring any obligation to make such changes and modifications

on Watts products previously or subsequently sold.

Testing

For field testing procedure, refer to Watts installation sheets

IS-TK-DP/DL, IS-TK-9A, IS-TK-99E and IS-TK-99D found on

www.watts.com.
For other repair kits and service parts, refer to our Backflow

Prevention Products Repair Kits & Service Parts price list PL-RP-

BPD found on

www.watts.com.

For technical assistance, contact your local Watts representative.

Local building or plumbing codes may require modifications to the

information provided. You are required to consult the local building

and plumbing codes prior to installation. If this information is not

consistent with local building or plumbing codes, the local codes

should be followed.
Need for Periodic Inspection/Maintenance: This product must

be tested periodically in compliance with local codes, but at least

once per year or more as service conditions warrant. Corrosive

water conditions, and/or unauthorized adjustments or repair could

render the product ineffective for the service intended. Regular

checking and cleaning of the product’s internal components helps

assure maximum life and proper product function.

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information

can result in death, serious personal injury, property

damage, or damage to the equipment.
Keep this Manual for future reference.

Installation Instructions

Series 007 and LF007

1

2

" - 2" (15 - 50mm)

Indoors -

Figure 1

Check local codes for installation requirements. Pipe lines should

be thoroughly flushed to remove foreign material before installing

the unit. A strainer should be installed as shown, ahead of backflow

preventer to prevent disc from unnecessary fouling. Install valve

inline with arrow on valve body pointing in the direction of flow.
For indoor installations, it is important that the valve be easily acces-

sible to facilitate testing and servicing. Do not install in a concealed

location.

CAUTION

!

Do not install with strainer when backflow preventer is used on

seldom-used water lines which are called upon during emergen-

cies, such as fire sprinkler lines, etc.
It is important that Series 007 and LF007 be tested periodically in

compliance with local codes, but at least once a year or more often

depending upon system conditions. Regular inspection, testing and

cleaning assures maximum life and proper product function.

NOTICE

Fire Protection System Installations
The National Fire Protection Agency (NFPA) Guidelines require a

confirming flow test to be conducted whenever a “main line” valve

such as the shutoff valves or a backflow assembly have been oper-

ated. Certified testers of backflow assemblies must conduct this

test. The trim valves of the confirming flow test. When the test is

completed, the trim valves must be returned to a fully open position.

Meter Box Installation