Installation, Installation drawings & dimensions – Watts OF240-4 User Manual
Page 3

3
Installation
1. Turn off all equipment to be fed by the OneFlow
®
System,
locate water supply cut-off valve and turn OFF
2. Determine if water line has an existing water treatment
system. If so, examine system for use of polyphospate or
other scale inhibitors. OneFlow
®
will not be effective if used
in conjunction with other scale inhibitors. Remove the scale
inhibitors from the water line or discontinue installation.
3. Install a
1
/
2
" full-flow ball valve on the water supply side that
will feed the water system.
4. Anchor the OneFlow
®
System on a wall stud or suitable
mounting material spanning wall studs. System must be
vertical and upright.
5. Run a suitable line from the
1
/
2
" full-flow ball valve at the
tap water source to the inlet ball valve on the left side of
the OneFlow
®
system. Use 2-3 wraps of Teflon
®
tape and
brace the inlet ball valve on the system with a wrench
when connecting the feed water line.
NOTE: DO NOT
OVERTIGHTEN CONNECTION FITTING INTO BALL VALVE.
6. Select the appropriate size tubing for the equipment being
fed and connect it to the outlet of the OneFlow
®
System.
NOTE: DO NOT connect the tubing to the equipment at
this time. Prior to making connection to the equipment
this line will be used to facilitate flushing the system. As
an option, a drain valve in a tee on the outlet side of the
OneFlow
®
system could be provided in the line to facilitate
flushing when changing filters.
7. With System inlet valve closed, slowly open the
1
/
2
" full-flow
ball valve at the tap water source. Check for leaks.
8. If a drain valve was not installed on the outlet side of the
system, hold the tubing that will connect to equipment in
a clean bucket or over sink or drain. Open the system inlet
feed valve and allow water to flush through system for 2
minutes at the specified system flow rate to allow air and
any carbon fines to escape.
NOTE: NO ACTIVATION IS
REQUIRED FOR THE OneFlow
®
SYSTEM TO PERFORM
PROPERLY. FLUSHING IS RECOMMENDED TO ALLOW
AIR TO ESCAPE THE SYSTEM AND REMOVE ANY
CARBON FINES PRIOR TO CONNECTING TO EQUIPMENT.
9. Make certain that the end of the tubing to be connected to
the equipment is clean and sanitary.
10. Connect tubing to equipment. Open all water supply valves
and check for leaks.
11. If no leaks, turn on equipment and check for normal operation.
12. Attach the Service Log to the installed OneFlow
®
system
and fill in install date.
Installation Drawings & Dimensions
Clearance