the burner output. The ZC output is energized.

The controller continues to monitor the system

and automatically restarts if the error condition

clears. Refer to Table 4.

The operating sequence for the L7248 is shown in

Table 5.

Figure 14: Setpoints and Differentials

G. HIGH LIMIT CONTROLLER
The High Limit opens and turns off the burner when

the water temperature reaches the setpoint. The

High Limit automatically resets after the water

temperature drops past the setpoint and through the

Differential. The L7248 models have High Limit

Differential presets of 15°F (8°C). See Figure 14.

6.

REMOVE GUN ASSEMBLY

LE Boilers equipped with Beckett AFG burners. Items

to be checked are nozzle size, type, and angle; head

size, (and setting on MD(V1) head); gun setting; and

positioning of electrodes. This information is shown in

Figure 15, and Table 6. If the desired boiler firing rate

is 0.6 GPH, the nozzle must be changed out, the low

firing rate baffle must be installed and the factory

settings must be changed according to Table 6. These

parts are in the bag attached to the burner. Reinstall

gun assembly.

LE Boilers equipped with Riello 40 F3 and 40 F5

burners: Items to be checked are nozzle size, type and

angle: settings (air gate, turbulator and pump pressure).

This information is shown in Table 6A. Reinstall gun

assembly.

7.

ADJUST OIL BURNER BEFORE STARTING

A. SET BURNER SETTINGS, see Tables 6 and 6A.
B. OPEN ALL OIL LINE VALVES.

Figure 1: "L1" and "V1" Head Electrode Positioning and Gun Setting (Beckett AFG)