Figure 1: L48 Circuit Board Layout -

Horizontal Mount

E. DISPLAY READOUT
In the

RUN mode, the Aquastat will flash "bt"

(boiler temp) followed by the temperature (i.e.,

220), followed by °F or °C.

To read boiler settings, press the I key to read the

parameter of interest. For example, press I High

Limit (HL) is displayed, followed by a three-digit

number, i.e., 220, followed by °F or °C. See

Display Readout, Figure 13.

Figure 13: Display Readout Definitions

After approximately 60 seconds without any key

presses, the display will enter a dim display mode.

To return to the bright display mode, simply press

any key.

F. OPERATION
The L7248 model is restricted to three operational

states - Normal, High Limit and Error. The

controller moves back and forth from High Limit to

Normal state as part of normal operation.

The controller will enter the Error state when there

is an abnormal condition. The operating states are:

(1) Normal: Boiler temperature went below the

High Limit setting (minus the Differential) and

has not exceeded the High Limit setting; or the

boiler temperature went above the Low Limit

setting and has not gone below the Low Limit

setting (minus the Differential).

(2) High Limit: Boiler temperature went above the

High Limit setting and has not dropped below

the High Limit setting (minus the Differential).

Error

Code

Cause / Action

Err1

Sensor fault; check sensor.

Err2

ECOM fault; check EnviraCOM™ wiring.

Err3

Hardware fault; replace control.

Err4

B1 fault; check B1 wiring/voltage.

Err5

Low Line; check L1-L2, 110 Vac.

Err6

Fuse; check ECOM wires, replace fuse.

Err7

EEPROM, HL, Hdf; reset to default values.

Restore desired settings.

Err8

Repeated B1 fault (voltage present at B1 when

output is turned off); check B1 wiring/voltage.

TABLE 4: LED ERROR CODES

(3) Error: The controller has detected an error

condition (e.g., open sensor) and has shut down

Action

System Response

Thermostat

calls for heat.

Circulator starts when water temperature

is above Low Limit setting (if applicable).

Boiler temperature is checked. Burner

starts when water temperature is below

High Limit setting.

Boiler

exceeds the

High Limit.

Burner is turned off. Burner restarts when

the water temperature drops below the

High Limit setting minus the Differential.

Thermostat is

satisfied.

Circulator and burner turn off.

Error

condition 1-5.

If an error condition is detected, all outputs

except ZC are shut down. Burner is off.

Control continues to function and restarts

when error is corrected.

During the error check sequence, the

system checks for drift in the sensor and

corrosion in the connections.

Error

condition 6.

EnviraCOM communication is not

available.

Error

condition 7.

The control has reset the High Limit

setting to a default setting and will

continue to run at those settings.

Performance of the system will be

degraded.

Error

condition 8.

If the error condition is detected, all

outputs except ZC are shut down. Burner

is off. Control continues to function and

restarts when all three user keys have

been pressed longer than 60 seconds.

TABLE : L48 CONTROLLER OPERATING

SEQUENCE