20

2.

Professionally install module.

3.

Add 1 % of the temperature span to the selected "minimum"
temperature and set this value on a PT 100 simulator (when
using a precision resistance decade, where necessary ob-
serve DIN IEC 751 conversion table from °C to

!) and cali-

brate the signal conditioner output signal to 0.200 mA using
the null potentiometer. (The potentiometers are located be-
hind the hinged cover).

4.

Set the "maximum" selected temperature on a PT 100 simu-
lator (or precision resistance decade) and calibrate the signal
output to 20.000 mA using the Span potentiometer.

5.

Repeat steps 3 and 4 (approx. 2-3 times), until the required
accuracy is achieved.