Interface Connections (Cont.)
Enable/Disable Control of Maxi Module Arrays
When using the Enable/Disable function on an output that consists of two or more Maxi
modules, it is necessary to connect the E/D pins of the corresponding module locations
together such that both modules are commanded to turn ON or OFF simultaneously.
Example: Slots 1 through 6 have been configured as a single output parallel array
(see Fig. 6)
In order to disable this array, E/Ds 1 through 6 should be shorted together as shown in
Fig. 6. With the E/Ds connected together, a single switch can then be used to remotely
enable and disable the output.
**Note:
Note: For single output power supply configurations, the simplest method of remotely
enabling and disabling the output is to use the General Shutdown (GSD) function.
Figure 6.
Enable/Disable Control
of Maxi Arrays