Application Tips

Remote Sense

A remote sense feature is provided on outputs configured with Mini or Maxi sized DC-DC

converters. The output sense connections must be terminated either locally or remotely and

may not be left open. VIPACs provided with the optional LugMate connectors are

configured for local sensing via removable jumpers installed at the factory. The jumpers will

need to be removed if access to the secondary control function is made via mating

connector 16385 and connections will need to be established for local or remote sensing.

Hold-up Capacitors

Hold-up capacitors can be located remotely with up to 3' of cable. Vicor applications

engineering should be consulted for projects requiring greater separation.

Wire Routing

Avoid routing wires over the VIPAC Power System.

Do not bundle Input and Output leads together.

Crimping Tool

The VIPAC can be configured with parallel modules for increased power or redundancy.

When output terminations other than the LugMate are specified the user must

properly connect the output and sense terminals. At no time operate a paralleled

output with a load applied to only one module! (See Output Connection Options)

Amp Hand Tool P/N

Die Set #

Wire Size

91508-1

20-18 AWG

91506-1

16-14 AWG

69710-1

58380-1

12 AWG

58380-2

10 AWG

Parallel Outputs