TCI HGA Quick Start User Manual
Page 7

7
9) Current Polarity – 2
• Navigate to Status screen
• Navigate to Line/Load status
• Verify that “Volts,” “Current,” “Power,”
“I THD," and “V THD” match expected values
for the power system
• If they do not, verify CTs are correctly installed
Warning
Improper operation and damage may
occur if CTs are installed incorrectly.
10) Final setup
• Press “Setup” to navigate to Setup screen
• Press “Harmonic Correct En” to enable
harmonic correction
• If unit is sized with sufficient capacity to
provide power factor correction, press
“PF Correct En”
• Press “Auto Start En” to enable Autostart
Warning
When Auto Start is enabled unit may
operate without operator input.
• Press “Save Settings” to save settings
and restart converter
• Let the unit come on automatically (about 30 s)
11) Final check
• Navigate to Status screen
• Navigate to Line/Load status
• Note the corrected voltage, current, power and
THD