TCI HGA Quick Start User Manual
Page 5

5
 
NOTE: Built In Sensor Wiring Error Detection 
• The active filter has an automatic sensor wiring
error detection algorithm built in to the 
controls. 
• If a sensor wiring error is detected please
reference the Sensor Error Auto Detection 
section of the full user manual available at 
www.transcoil.com. 
 
3) Home screen check 
• Compare “Freq” to expected line frequency 
• Compare “Supply Voltage” to expected 
line voltage
• “Current” expected to be zero because unit is
not running and CT inputs are shorted
• If status indicates a Fault, press “Stop” button
to reset condition
 
4) Status screen check 
• Press “Status” to navigate to Status screen 
• Compare “Volts” to expected line voltage 
• Compare “Freq” to expected line frequency 
• “Current” expected to be zero if unit is not
running and CT inputs are shorted
 
5) Phase rotation check 
• Press “Phase to Neutral Voltage Plot” 
• Check that the current peaks follow the 
following sequence from left to right: Phase A 
(green), Phase B (blue), Phase C (red) 
• Equipment is phase rotation sensitive, if phase
rotation is incorrect, power down unit and 
rewire to adjust phase rotation by swapping 
two incoming phase connections 
Warning
Improper operation will occur when 
input voltage phase rotation is 
incorrect. 