Installation, Minimum alcove clearance to combustible materials, Additional clearances for backwall exit – Regency Hampton H300 Large Wood Stove User Manual
Page 10

10
Hampton H300 Cast Freestanding Woodstove
INSTALLATION
MINIMUM ALCOVE CLEARANCE TO
COMBUSTIBLE MATERIALS
This Hampton Freestanding model has been alcove approved and must be installed
with a listed double wall connector to the ceiling level.
Note: Minimum alcove ceiling height (from fi nished fl oor) - 60" (1525 mm)
Maximum depth of alcove - 48" (1220 mm)
From From Flue Min. Min.Hearth
Unit (with Heat Shield)
Unit
Center-line Width to Rear Wall
G H
I J K L
H300
15" (381 mm) 13" (330 mm) 28" (711 mm) 13" (330 mm) 57" (1448 mm) 51-1/4"
without side load door
(1301 mm)
ADDITIONAL CLEARANCES
FOR BACKWALL EXIT
Note: Floor Protection must extend 2" (50mm)
to each side of the elbow.
Note: If side load door is used, fl oor protection
must extend at least 18" (457mm) from
the side of the unit.
Minimum Clearance to Non-Combustibles
From
Unit (with Heat Shield)
Unit
A B
H300
min. 0" (0 mm) 15" (381mm)
max. 9" (228 mm)
60" (1524 mm)
with side load door
Minimum Clearance to Combustibles
From
Unit (with Heat Shield)
Unit
A B
H300
9" (228 mm) 15" (381 mm)
Min. Mantel Height (from fi nished fl oor):
48" 1219 mm
Max. Mantel Depth:
12" 305 mm