8

F5100 Regency Freestanding Woodstove

INSTALLATION

MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS

Please read the section below carefully as clearances depend on whether the Airmate or the Rear Heat Defl ector is installed on the stove.
Measurements "From Unit" are from the top plate of the stove to a side wall or to a corner, and from the rear heat shield to a back wall.

Clearances may only be reduced by means approved by the regulatory authority.

Note: Minimum ceiling height roof exit - 83" (2108 mm)

B

A

D

E

F

F

C

C

NOTE:

Be aware that local Codes and
Regulations may override some
clearances listed in this manual.

Check with your local inspector.

Residential Close Clearance (To be installed with required pipe components) Listed Double Wall Pipe

When the stove is installed as a close clearance residential unit, a listed double wall connector is required from the stove collar to the ceiling level.

F5100

with Airmate or
Rear Defl ector

A

B

C

D

E

F

11"

279mm

10"

254mm

8"

203mm

25-1/2"

648mm

17-1/8"

435mm

22-1/2"

572mm

Mobile Home Close Clearance (To be installed with required pipe components) Listed Double Wall Pipe

When

the stove is installed as a close clearance residential unit, a listed double wall connector is required from the stove collar to the ceiling level.

Refer to Mobile Home Installation in this manual.

F5100

with Airmate or
Rear Defl ector

A

B

C

D

E

F

11"

279mm

10"

254mm

8"

203mm

25-1/2"

648mm

17-1/8"

435mm

22-1/2"

572mm"

Minimum Alcove Clearance to Combustible Materials

The Regency Freestanding models have been alcove approved and must be installed
with a listed double wall connector to the ceiling level.

Note: Minimum alcove ceiling height - 83" (2108 mm) Vertical Termination}

H = Maximum depth of alcove - 48" (1219 mm)

G= Minimum width of alcove - 63" (1600 mm)

B

A

D

E

H

G

ROOF EXIT
WALL EXIT

ROOF EXIT
WALL EXIT

ROOF EXIT
WALL EXIT

NOTE:

Approved with Listed Double Wall
pipe only. Do not use single wall
pipe.

NOTE:

Clearances to combustibles are for

the safety of the property. To avoid
overheating and damaging the
appliance these clearances should
be maintained for non-combustibles
also.