GP-MSEM-BX-06A

SEM(U) / IT(U) Manual

RD: Aug 2006

RL: 06A

KH

SPARK STOPS WHEN
BURNER LIGHTS

SYSTEM RUNS UNTIL CALL
FOR HEAT ENDS

CALL FOR HEAT ENDS:
SYSTEM SHUTS OFF

YES

YES

YES

YES

NO

NO

NO

NO

SPARK IGNITER MAY BE OUT OF POSITION
CHECK ELECTRICAL CONNECTION FROM IGNI

TION CONTROL PIN #2 TO GAS VALVE.

CHECK FOR 110 VAC ACROSS GAS VALVE IF

OKAY, REPLACE GAS VALVE.

CHECK GROUND WIRE, IGNITER AND HT CABLE.
CHECK THAT BURNER FLAME COVERS ELECTRODE
IF CHECKS ARE OKAY, REPLACE IGNITION CONTROL


NOTE: IF IGNITION CONTROL GOES INTO LOCKOUT, MODE
RESET THE SYSTEM.

NOTE: IF GROUND IS POOR OR ERRATIC, SHUTDOWNS

MAY OCCUR OCCASIONALLY EVEN THOUGH OPERA-
TION IS NORMAL AT THE TIME OF CHECKOUT.

CHECK GROUND WIRE NECTIONS AND CONTINUITY.
IF CHECKS ARE OKAY, REPLACE IGNITION CONTROL

CHECK FOR PROPER TEMPERATURE CONTROLLER

OPERATIONS

REMOVE VALVE LEAD AT IGNITION CONTROL, IF VALVE

CLOSES, RECHECK TEMPERATURE CONTROLLER AND
WIRING, IF NOT, REPLACE GAS CONTROL OPERATOR

TROUBLESHOOTING ENDS

CONTINUED FROM PREVIOUS PAGE

MAIN BURNER LIGHTS