B.2 RS-422 Cable Configuration

B.2.1 RS-422 Connection




TxD

RxD

TxD-

RxD-

TxD

RxD

6

7

RxD'

TxD'

DB9 male connector

2

3

Series PM-280/288/270/290

Powermeters

RxD-

TxD-

RxD

TxD

6

7

DB9 male connector

RxD-

TxD-

RxD

TxD

Series PM-290H Powermeters

Series PM-170 Powermeters

8

9

14

15

16

17

DB25 male connector

1

1

1

GND

GND

GND

* A termination resistor should only be connected at the furthest end of the cable

COM

R1

R1,R2 - 120

*R2

R3,R4 - 1.2 k

**R3

**R4

** In RS-422 communication, a reference or common line should be used in addition to signal lines

use a reference line, place pull-down resistors R3 and R4 on both outputs of the driver to avoid

leaving the line floating when the line is idle