SATEC 1771DB User Manual
Page 14
14
Table A-2 Data set #2
Field Field Name
BTR buffer word
Units
Value evaluation
Range
No.
LO
HI
SIGN
formula
1
Instrument address
1
LO
1 - 31
2
Voltage A
2
3
V
3
Voltage B
4
5
V
HI*10000+LO
0 - 999,000
4
Voltage C
6
7
V
5
Current A
8
A
6
Current B
9
A
LO
0 - 60,000
7
Current C
10
A
8
Active Power A
11
12
13
kW
HI*10000+LO
9
Active Power B
14
15
16
kW
SIGN = 0 means '+'
±
0 - 5,184,000
10
Active Power C
17
18
19
kW
SIGN = 1 means '-'
11
Power Factor A
20
21
LO/100
12
Power Factor B
22
23
SIGN = 0 means '+'
±
0 - 1.00
13
Power Factor C
24
25
SIGN = 1 means '-'
14
Total Active Power
26
27
kW
HI*10000+LO
0 - 5,184,000
15
System Power Factor
28
29
LO/100
SIGN = 0 means '+
SIGN = 1 means '-'
±
0 - 1.00
16
Active Energy
30
31
kWh
HI*10000+LO
0 - 99,999,000
17
Unbalanced Current
or Ground Leakage
32
A or
mA
LO
0 - 60,000
18
Frequency
33
Hz
LO/10
45.0 - 65.0
19
Reactive Power A
34
35
36
kvar
HI*10000+LO
20
Reactive Power B
37
38
39
kvar
SIGN = 0 means '+'
±
0 - 5,184,000
21
Reactive Power C
40
41
42
kvar
SIGN = 1 means '-'
22
THD of Voltage A
43
%
23
THD of Voltage B
44
%
24
THD of Voltage C
45
%
LO/10
0 - 99.9
25
THD of Current A
46
%
26
THD of Current B
47
%
27
THD of Current C
48
%
28
Reactive Energy
49
50
51
kvarh
HI*10000+LO
SIGN = 0 means '+'
SIGN = 1 means '-'
-9,999,000 -
99,999,000
29
Total Reactive Power
52
53
54
kvar
HI*10000+LO
SIGN = 0 means '+'
SIGN = 1 means '-'
±
0 - 5,184,000
30
Total Apparent
Power
55
56
kVA
HI*10000+LO
0 - 5,184,000
31
Active Power
Maximum Demand
57
58
kW
HI*10000+LO
0 - 5,184,000
32
Accumulated Active
Power Demand
59
60
kW
HI*10000+LO
0 - 5,184,000
33
Ampere Maximum
Demand A
61
A
34
Ampere Maximum
Demand B
62
A
LO
0 - 60,000
35
Ampere Maximum
Demand C
63
A
36
Error code (in version
with E option)
64
LO
see Table 4-1