PM135 QuickStart

www.satec-global.com

CONFIGURATION

The essential configuration includes:

1. Basic measurement setup
2. Communication setup and testing
3. Resetting the min/max, energy, demands etc.

Additional recommended configuration: set points, TOU and data logging
Note: It may be easier to configure communication first and use PAS software for setup

Basic Measurement Setup

In any display screen, press MENU

  

to enter the Basic Settings Display.

Parameter

Description

Default

Wiring Mode (see below)

Network wiring configuration

4LN3

PT Ratio

Transformation ratio of the Potential Transformers

1

PT Ratio Multiplier

Additional PT factor for EHV network

X1

CT Primary Current

The Primary Rating Of The Current Transformers

5A

Power Demand Period
(E & EH models)

Duration in minutes of the power demand period
calculations. E = External pulse in DI1.

15

Blocks in Sliding Demand
(E & EH models)

The number of blocks to be averaged for sliding window
demands

1

Volt/Ampere Demand Period

Duration in seconds for voltage and current demand

900

Nominal Frequency

The nominal frequency

60 Hz

Max. Demand Load Current

0 = CT primary current. Other = max. current

0

Wiring Mode

Setup

3-wire 2-element Delta direct connection using 2 CTs

3DIR2

4-wire 3-element Wye direct connection or 3PTs, and 3 CTs

4LN3 or 4LL3

*

3-wire 2-element Open Delta connection using 2 PTs, 2 CTs

3OP2

4-wire 2½-element Wye connection using 2 PTs, 3 CTs

3LN3 or 3LL3

*

3-wire 2½-element Open Delta connection using 2 PTs, 3 CTs

3OP3

4-wire 3-element Delta direct connection using 3 CTs

4LN3 or 4LL3

*

3-wire 2½-element Broken Delta connection using 2 PTs, 3 CTs

3bLN3 or 3bLL3

*

* LN or LL denotes the default use of L-L or L-N voltages (in thresholds, min/max, demands etc.)

Communication setup and testing

In any display screen, press MENU

5 times

and

to setup the built in RS-485 port

(COM1). If communication module is present, configure also COM2.

Resetting the min/max, energy, demands etc.

Press MENU

to enter the reset menu. Select the value to be reset, press

to

select, then press

for 5 seconds until the "Do" notification is changed to "Done".