SATEC PM130 PLUS Quick Start User Manual
Page 4

PM130 PLUS QuickStart
www.satec-global.com
CONFIGURATION
The essential configuration includes:
1. Basic measurement setup
2. Communication setup and testing
3. Resetting the min/max, energy, demands etc.
Additional recommended configuration: set points, TOU and data logging
Note: It may be easier first to configure communication and use PAS software for setup
Basic Measurement Setup
In any display screen, press SELECT x 3 (until
blinks), then press ENTER
(
blinks),
then
x 2
()
and ENTER to enter the Basic Settings Display.
Parameter
Description
Default
(see below)
Network wiring configuration
Transformation ratio of the Potential Transformers
.
Additional PT factor for EHV network
The Primary Rating Of The Current Transformers
(quick access to this parameter: press SELECT, then simultaneous
and SELECT)
. (E & EH models)
Duration in minutes of the power demand period calculations
E = External pulse in DI1
. (E & EH models)
The number of blocks to be averaged for sliding window demands
.
Duration in seconds for voltage and current demand
The nominal frequency
Max. Demand Load Current in Amperes. 0 = CT primary current.
Wiring Mode
Setup
3-wire 2-element Delta direct connection using 2 CTs
4-wire 3-element Wye direct connection or 3PTs, and 3 CTs
or
*
3-wire 2-element Open Delta connection using 2 PTs, 2 CTs
4-wire 2½-element Wye connection using 2 PTs, 3 CTs
or
*
3-wire 2½-element Open Delta connection using 2 PTs, 3 CTs
4-wire 3-element Delta direct connection using 3 CTs
or
*
3-wire 2½-element Broken Delta connection using 2 PTs, 3 CTs
or
*
* LN or LL denotes the default use of L-L or L-N voltages (in thresholds, min/max, demands etc.)
Communication setup and testing
In any display screen, press SELECT x 3
(
blinks), then press ENTER
(
blinks),
then
x 3
(
.
) and
ENTER to setup the built in RS-485 port (COM1).
If communication module is present, configure also COM2.
Resetting the min/max, energy, demands etc.
In any display screen, press SELECT x 3 (
blinks), then press ENTER
(
blinks), then
ENTER to enter the reset menu. Select the value to be reset, press SELECT
to select, then press
ENTER for 5 seconds until the notification is changed to .