Wiring the CO Detector to a Controller
WARNING: Always verify that power to the controller is OFF before you make wiring
connections.
1.
Turn off the controller.
2.
Turn off or unplug power to the controller.
3.
If the detector is mounted remotely from a controller using the junction box, proceed
to step 4.
If the detector is mounted directly to a controller, it is normally factory wired. Confirm
that the detector’s black and red wires are connected to the appropriate controller
detector terminals and skip to “Start Up” on page 7. See Figure 4, the controller
operator’s manual, and the controller’s detector head specification sheet for the 65-
2496RK detector for the wiring connections.
4.
Remove the junction box cover.
5.
Guide a two-conductor, shielded cable or two wires in conduit through the unused
conduit hub of the junction box. Use appropriate conduit fittings and construction
technique for the environmental rating of the junction box. The junction box is rated
NEMA 4X.
6.
Connect the two wires to the detector using the terminal block.
CAUTION:
If using shielded cable, leave the drain wire insulated and disconnected at the
detector. You will connect the opposite end of the cable’s drain wire at the controller.
7.
Secure the junction box cover to the junction box.
8.
Route the cable or wires leading from the CO detector through one of the conduit
hubs at the controller housing. Use appropriate conduit fittings and construction
technique for the environmental rating of the controller. RKI controllers are typically
rated NEMA 4X.
CAUTION:
Do not route power and detector wiring through the same conduit hub. The power
cable may disrupt the transmission of the detector signal to the controller.
9.
Connect the wires to the applicable controller terminal strip. See the controller
operator’s manual and the controller’s detector head specification sheet for the 65-
2499RK detector.