Overview, Specifications – RKI Instruments 65-2432RK-05 User Manual
Page 5

65-2432RK-05 CO Transmitter • 1
Overview
This manual describes the carbon monoxide (CO) transmitter. This manual also describes
how to install, start up, maintain, and calibrate the transmitter. A parts list at the end of
this manual lists replacement parts and accessories for the CO transmitter.
Specifications
WARNING: Do not use this product in a manner not specified in this instruction
manual.
Table 1 lists specifications for the CO transmitter.
NOTE: The following symbol on the detector label is a caution to the user to refer to this
documentation for installation and operation instructions:
WARNING: When using the 65-2432RK-05, you must follow the instructions and
warnings in this manual to assure proper and safe operation of the
65-2432RK-05 and to minimize the risk of personal injury. Be sure to
maintain and periodically calibrate the 65-2432RK-05 as described in this
manual.
Table 1: Specifications
Target Gas
Carbon Monoxide (CO)
Area Classification
Explosionproof for Class I, Groups B, C, and D
Temperature Code
T6
Installation Category
Installation Category 1. Signal level, special equipment or parts of
equipment, telecommunication, electronic, etc., with smaller
transient overvoltages than Installation Category (Overvoltage
Category) II (ref. IEC 664).
Input Voltage
11 VDC - 30 VDC
Sampling Method
Diffusion
Signal Output
4 to 20 mA
Detection Range
0 to 300 PPM (parts per million)
CO Detector Signal Output
0.3 mA at 0 ppm CO nominal
2.5 mA at 300 ppm CO nominal
Response Time
90% in 30 seconds
Accuracy
± 5% of reading or ± 5 ppm CO (whichever is greater)
Operating Temperature
23°F to 104°F (-5°C to 40°C)
!